Figure B5-46. Two Opening Ducted Method
C. One Opening Method (Figure B5-47) - One permanent opening,
commencing within 12 inches of the top of the enclosure, shall be provided.
1. The equipment shall have clearances of at least 1 inch from the sides and
back and 6 inches from the front of the appliance.
2. The opening shall directly communicate with the outdoors and shall have
a minimum free area of 1 square inch per 3000 BTU's per hour of the
total input rating of all equipment located in the enclosure, and not less
than the sum of the areas of all vent connectors in the confined space.
3. Refer to the NFGC, Section 8.3 for additional information.
GAS
VENT
CLEARFIRE
BOILER
WATER
HEATER
GAS
VENT
EXTERIOR WALL
INTERIOR WALL
FRESH AIR
INLET DUCT
OUTLET AIR DUCT
12" MINIMUM
12" MINIMUM