background image

 

10 

START-UP & CALIBRATION                                       

CHAPTER 7 

The  previous  sections  of  this  manual  have  involved  comparatively  static  procedures  –  making 
electrical  connections and fitting pipe,  etc.  This section involves the dynamic process of starting up 
and  balancing  the  components  of  the  system,  including  initiating  water  flow,  making  air  and  water 
flow adjustments, etc. 

 

Maximum  performance  and  reliability  is  achieved  when  the  prescribed  air  flow  and  vacuum  or  pressure  levels  are 
maintained  at  the  HDO3  system  while  the  ozone  injector  is  operating  at  a  comparatively  higher  vacuum  (measured  in 
inches of mercury, or “in.Hg”).  Also, maintaining the correct  water flow and hydraulic pressures will ensure the highest 
possible level of dissolved ozone. The air from the air preparation system of the HDO3-I and HDO3-II flows toward the 
ozone generator under pressure, and from the ozone generator under vacuum (created by the ozone injector). The change 
from  pressure  to  vacuum  occurs  at  the  SCFH  meter  of  the  air  preparation  system  located  on  the  bottom  left  side  of  the 
HDO3 system. Where as, the air from the air preparation system of the HDO3-III is flowing 

through

 the ozone generator 

under  pressure,  and 

from

  the  ozone  generator  under  a  slight  vacuum  (created  by  the  ozone  injector).  The  change  from 

pressure to vacuum occurs after the stainless steel “Ozone Injector–Vacuum Control” needle valve located on the control 
panel of the HDO3-III. 

 

HDO

3

 Series – Dissolved Ozone Generation System 

Warning:

 

Disconnect  the  External  Loop  dry  contact  (see  Appendix-Section  A)  from  the  ozone  generator 

while performing all start-up procedures.

 

Failure to do so may result in ozone escaping to atmosphere. 

Step 1: 

Make sure  all isolation valves in the ozone water system are open (Figures 4-2 and 4-3 show recommended 
isolation valve locations). 

Step 2: 

The main power switch of the HDO3 system, located on the Control Panel (see Appendix-Section A), should 
be in the “OFF” position. Main power should be available to the HDO3 system. 

Step 3:

 

Remove the Fill Port Cap of the vacuum break located on the backside of the HDO3 system and fill the Riser 
Tube with clean water (no particulate matter) to the fill level, see Appendix-Section A 

Step 4:

 

Re-install the Fill Port Cap, hand tight. 

Note:

 

Do not over tighten as damage to PVC fittings may occur.

 

Step 5: 

Completely  open  the  contact  tank  backpressure  valve,  located  towards  the  bottom  backside  of  the  HDO3 
system (see Appendix-Section A), by turning it counter-clockwise. 

Step 6: 

Start-up hydraulics. Allow the water in the system to reach hydraulic equilibrium (contact vessel full, off-gas 
vent operating, etc.) and observe for plumbing leaks. If the inlet water supply is not under pressure be sure the 
HDO3 booster pump is flooded with water so that the booster pump will prime. 

Notes: Water flow 

must

 be 

established  through the  HDO3 system booster pump before operation. If the inlet  water supply to the 
HDO3  system  is 

not

  under  pressure  the  system  may  not  completely  fill  with  water  until  the  HDO3 

system is operational. 

Step 7:

 

If the inlet water supply to the HDO3 system is pressurized, using a water pressure  regulator  with a pounds 
per  square  inch  (PSI)  gauge,  regulate  the  inlet  water  supply  pressure  to  20PSI  maximum. 

Note: 

Backpressure 

downstream

 of the HDO3 system could affect this PSI reading. 

 

Step 8:

 

Disconnect the green oxygen delivery line from the oxygen concentrator, located on the bottom left-hand side 
of the HDO3 system. 

Step 9: 

Turn the main power switch of the HDO3 to the “ON” position. The HDO3 should energize giving power to 
the booster pump, oxygen concentrator, ozone generator and dissolved ozone monitor/controller. 

Step 10: 

Adjust  the  oxygen  concentrator  flow  meter  located  on  the  bottom  left-hand  side  of  the  HDO3  system.  This 
standard  cubic  feet  per  hour  (SCFH)  air  flow  meter  must  be  set  to  atmospheric  pressure.  See  the  “Air 
Preparation  Air  Flow”  line  of  the  Operating  Parameters  chart  Figure  7-2  for  the  set  point  of  each  HDO3 
system. 

Note:  When  the  system  is  in  normal  operation  the  SCFH  flow  meter  setting  may  drop  due  to 

backpressure through the system.  Do 

not

 re-adjust the flow meter. 

Step 11: 

Reconnect the green oxygen delivery line to the oxygen concentrator, which was removed in Step 7 above. 

Step 12: 

Switch the ozone generator power switch to the “ON” position located on the bottom of the ozone generator, 
see Appendix-Section A. 

Step 13: 

If  the  inlet  water  supply  to  the  HDO3  system  is  under  pressure,  slowly  close  the  contact  tank  backpressure 
valve until the needle of the “Low Pressure – Side Water” gauge reaches 20PSI.  If the inlet water supply is 
not under pressure slowly close the contact tank backpressure valve until the needle of the “Low Pressure – 
Side Water” gauge is between 1-5PSI.

Step 14: 

Adjust the feed gas flow meter, located on the Control Panel (see Appendix-Section A), of the HDO3 system. 
See the “Feed Gas Flow Rate” line of the Operating Parameters chart Figure 7-2. 

Summary of Contents for HDO3-I

Page 1: ...ne Generation System ClearWater Tech LLC Integrated Ozone Systems 850 E Capitolio Way San Luis Obispo Ca 93401 805 549 9724 Fax 805 549 0306 E mail service cwtozone com www cwtozone com Copyright 2005 ClearWater Tech LLC Reproduction of any kind is prohibited LIT210 REV121605 ...

Page 2: ...y low pneumatic pressures minimizing noise and reducing compressor wear The air preparation system affects ozone production in grams per hour and more importantly ozone concentration also known as percent by weight Since ozone is produced with oxygen the greater the percent of oxygen that enters the ozone generator will produce more grams per hour and concentration of ozone Since the HDO3 Series o...

Page 3: ...fficient contacting of the ozone gas with the water and off gas any residual ozone By design the operating water pressures of this system and the ClearWater Tech engineered contacting system allows for high levels of dissolved ozone to be maintained in the water in this single pass configuration The HDO3 systems incorporate a water pressure relief valve and positive atmospheric vacuum break as sta...

Page 4: ...ry distinctive odor and is detectable at very low concentrations 0 02 ppm which is far below OSHA s maximum permissible exposure level of 0 1 ppm HIGH VOLTAGE WARNING CLEARWATER TECH OZONE GENERATORS OPERATE AT HIGH VOLTAGE DO NOT TAMPER WITH OR DELIBERATELY BYPASS THE COVER OR SAFETY SWITCHES BUILT INTO THE OZONE GENERATOR UNLESS INSTRUCTED TO DO SO BY THIS MANUAL IF CONTACT IS MADE WITH OPERATIN...

Page 5: ...e electrical supply for this product must include a suitably rated switch or circuit breaker to open all ungrounded supply conductors to comply with Section 422 20 of the National Electrical Code ANSI NFPA 70 1987 The disconnecting means must be readily accessible to the operator s but installed at least five feet from any open body of water 8 Be sure to bond ground the system using the copper bon...

Page 6: ...equired No caustic chemicals should be stored in the area surrounding the equipment A minimum clearance of six inches from the vents on either side of the ozone generator is required The equipment is heavy and requires proper support Therefore a clean dry level surface should be provided for the HDO3 Series systems The HDO3 Series systems are designed for specific voltage requirements and to withs...

Page 7: ... fpt 1 fpt 1 1 4 fpt 1 fpt Step 1 Arrange the HDO3 system according to mechanical print or as dictated by equipment layout and serviceability considerations Do not secure the system to equipment pad at this point Dry fit plumbing as appropriate to insure proper fit and location before making permanent connections Step 2 Install a tee or plumbing saddle into the main water line for the sidestream c...

Page 8: ...Installation Diagram Figure 4 3 HDO3 Dissolved Ozone System OPTIONAL Pressure Reducing Valve Optional Service Loop Isolation Valve Isolation Valve Isolation Valve Isolation Valve Main Water Line Sidestream Water Line HDO3 Dissolved Ozone System Isolation Valve OPTIONAL Pressure Reducing Valve ...

Page 9: ... 20mA board and the EXT LOOP LED and will again illuminate the Ozone Output LED s The external loop a removable two position plug with a white 18AWG wire located at the bottom panel of the ozone generator see Appendix Section A can be interfaced to any control device i e pressure switch vacuum switch flow switch float switch ORP controller PPM controller or timer To interface a control device to t...

Page 10: ...O3 series systems are equipped with an integral dissolved ozone monitor controller This monitor controller is equipped with alarm relays that can be used to interlock other devices based on dissolved ozone levels Main power and the 4 20mA control interface to the ozone generator have been pre wired at the factory The unit has also been pre programmed at the factory to supply a constant 20mA 100 oz...

Page 11: ...lve located towards the bottom backside of the HDO3 system see Appendix Section A by turning it counter clockwise Step 6 Start up hydraulics Allow the water in the system to reach hydraulic equilibrium contact vessel full off gas vent operating etc and observe for plumbing leaks If the inlet water supply is not under pressure be sure the HDO3 booster pump is flooded with water so that the booster ...

Page 12: ...observed in the vacuum break do NOT re connect the External Loop dry contact See Troubleshooting Guide Step 20 Approximately 20 seconds after the External Loop has been re connected the dissolved ozone monitor controller should begin registering a steady increase in the dissolved ozone level Adjust the dissolved ozone level by either setting the dissolved ozone controller to a desired set point or...

Page 13: ...ne Generator Vacuum Ozone Injector Vacuum High Pressure Side Water Water Supply Inlet Pressurized Non Pressurized 2 Low Pressure Side Water Water Supply Inlet Pressurized Non Pressurized 2 6 to 8 scfh 6 to 8 scfh 3 to 8 in Hg 5 to 25 in Hg 55 65 35 45 PSI 15 25 0 5 PSI 8 scfh 8 scfh 5 in Hg 15 in Hg 60 40 PSI 20 5 PSI HDO3 II Operating Range Optimum Air Preparation Air Flow flow meter left side of...

Page 14: ...Start Up and Calibration continued 13 Quick Reference Guide Rosemont Dissolved Ozone Monitor Controller Figure 7 3 ...

Page 15: ... Air Preparation Air Flow line of the Operating Parameters chart see Figure 7 2 This meter is set at atmospheric pressure see Start Up and Calibration steps 8 11 Ozone Generator Indicating Lights HDO3 I Only Check the indicator lights on the ozone generator See Figure 7 1A for Ozone Generator LED Display function Indicating Lights HDO3 II and HDO3 III Only Check for illumination of the drive modul...

Page 16: ...e inlet and outlet of the HDO3 system Semi Annual Procedures CAUTION Follow system shutdown procedures before performing any of the following steps Air Preparation System Air Inlet Filter Replace the air compressor inlet filter see Appendix Section A Note Manufacturers recommended replacement interval is 4 000 hours of operation Operating conditions in the equipment area will dictate the required ...

Page 17: ...ation of the end cap on the heat sink cathode assembly The stainless steel clamp on the HDO3 III reaction chamber end caps must not be removed Step 8 With contact brush attached remove the brush adapter nut from the high voltage end cap Step 9 Inspect the dielectric end caps and cathode for breakage corrosion or debris Clean and or replace parts as necessary Re assemble the reaction chamber per th...

Page 18: ...tion press the high voltage end cap onto the heat sink cathode assembly until flush with the heat sink cooling fins Note Orientation of the end cap on the heat sink cathode assembly Step 8 Slide the four end cap retaining screws through the holes in the end cap aligning them with the heat sink screw bosses Thread screws into screw bosses until heads are snug against the end cap Step 9 Re install c...

Page 19: ...l Clamp Contact Brush Brush Adapter Nut High Voltage End Cap and O rings End Cap Retaining Screw and Washer Oxygen Inlet Fitting Viton Washer Stainless Steel Washer High Voltage Lead Heat Sink and Cathode Ozone Outlet Fitting Bottom End Cap And O rings Heat Sink and Cathode Glass Dielectric High Voltage Anode Contact Brush Oxygen Inlet Fitting High Voltage Lead Brush Adapter Nut High Voltage End C...

Page 20: ...section Low fee gas flow rate above Make adjustments with the Feed gas Flow Rate needle valve and the Ozone Injector Vacuum Control knob High Pressure Side Water and Low Pressure Side Water gauges have Equalized Excessive backpressure downstream of the ozone injector or HDO3 system Ozone Generator Vacuum not High vacuum Slightly open the Ozone Injector within Operating parameters Control Vacuum Co...

Page 21: ...output control board pins are properly inserted into the output control board Main Power LED is not illuminated LED display board is inoperable Replace LED display board but all other LED s are illuminated Circuit breaker trips Incorrect wiring to HDO3 System See Installation Procedures Electrical Circuit breaker amperage does not Replace with correct circuit breaker match system draw See Installa...

Page 22: ...gh Pressure Side Water and Low Pressure Side Water gauges have Equalized Excessive backpressure downstream of the ozone injector or HDO3 system HDO3 III only Ozone Generator Pressure gauge is too high Slightly open the Ozone Injector Vacuum Control knob then adjust the Feed Gas Flow Rate meter Ozone Generator Vacuum not High vacuum Slightly open the Ozone Injector within Operating parameters Contr...

Page 23: ...n stream of the Remove backpressure downstream HDO3 system Low Pressure Contact tank backpressure valve is open Close the back pressuring valve slightly Dissolved Ozone Monitor Controller See the monitor controller I O manual not operating Ozone Generator Main Power light No power to HDO3 System Check main power to system is not illuminated or System is not Installation Procedures Electrical ON Lo...

Page 24: ...Replace drive board Failed drive transformer Replace drive transformer Broken dielectric Replace dielectric Water in ozone reaction chamber Clean dielectric and replace O rings Excessive dirt or debris in the ozone Clean dielectric and replace O rings reaction chamber Loose or disconnected High Voltage Tighten or Attach High Voltage lead lead to transformer to transformer High temp Limit See Troub...

Page 25: ...m of ozone injector Back pressure in hydraulic line Check for obstructions downstream of ozone injector Booster pump not functioning properly Check booster pump contact dealer Ozone smell detected around Insufficient vacuum at venturi See Start Up Calibration vacuum break or ozone injector Loose fittings Check all tighten as required Outlet water Supply Pressure Low Pressure Side Water gauge is in...

Page 26: ...System with out Cover AIR PREP UNIT OXYGEN OUTPUT SCFH HDO3 I Workhorse 8C 90 3 8 scfh 5PSI HDO3 II Workhorse 15C 90 3 15 scfh 5PSI HDO3 III Workhorse 12C 90 3 12 scfh 12PSI Cover Filter Front of Unit SCFH Air Flow Meter Oxygen Outlet Fitting Hour Meter Power Cord Compressor Inlet Filter Oxygen Concentrator Sieve Bed ATF Compressor Compressor Cooling Coil ...

Page 27: ...one Monitor Controller E Feed Gas Flow Rate F Ozone Injector Vacuum Control G Low Pressure Side Water H Main Power Switch OFF ON A F E D C B G H A Ozone Generator Pressure B Ozone Injector Vacuum C High Pressure Side Water D Dissolved Ozone Monitor Controller E Feed Gas Flow Rate F Ozone Injector Vacuum Control G Low Pressure Side Water H Main Power Switch OFF ON A B C D E F G H ...

Page 28: ...Break Fill Port Cap Contact Tank Ozone Generator Vacuum Break Water Pressure Relief Valve Behind Vacuum Break Dissolved Ozone Probe Main Power Cord Contact Tank Backpressure Valve Oxygen Concentrator Oxygen Concentrator Cooling Fan Vacuum Break Drain Barb Vacuum Break Fill Level Cover Filter Ozone Off Gas Line To Destruct System Vacuum Break Flapper Valve Booster Pump Oxygen Concentrator Flow Mete...

Page 29: ...0mA Connector Power Entry Module OFF ON Switch Cord Input Fuse Carrier Bonding Ground Lug Fan and Fan Filter Ozone Outlet LED Display Board Under Cover High Voltage Transformer Reaction Chambers High Voltage Drive Boards Board Retainer Bracket Output Control Board Inline Particulate Filter Main Mother Board Vacuum Switch Cover Safety Switch External Loop Remote 4 20mA Control Leads Connected to Di...

Page 30: ...m Break Fill Port Cap Contact Tank Ozone Generator Vacuum Break Water Pressure Relief Valve Behind Vacuum Break Dissolved Ozone Probe Main Power Cord Contact Tank Backpressure Valve Oxygen Concentrator Oxygen Concentrator Cooling Fan Vacuum Break Drain Barb Vacuum Break Fill Level Cover Filter Ozone Off Gas Line To Destruct System Vacuum Break Flapper Valve Booster Pump Oxygen Concentrator Flow Me...

Page 31: ...ower Supply Vacuum Switch 4 20mA Control Board Cover Safety Switch External Loop Remote 4 20mA Control Leads Connected to Dissolved Ozone Monitor Controller Air Prep Inlet Manual Ozone Output Adjustment Knob Main Power Light External Loop Connector Remote 4 20mA Connector Fuse Carriers Bonding Ground Lug Fan and Fan Filter Ozone Outlet Fitting Main Power Switch OFF ON Condulet Main Power Leads Ozo...

Page 32: ...um Break Fill Port Cap Contact Tank Ozone Generator Vacuum Break Vacuum Break Drain Barb Vacuum Break Fill Level Dissolved Ozone Probe Contact Tank Backpressure Valve Main Power Cord Oxygen Concentrator Oxygen Concentrator Cooling Fan Water Pressure Relief Valve Behind Vacuum Break Cover Filter Ozone Off Gas Line To Destruct System Vacuum Break Flapper Valve Booster Pump Oxygen Concentrator Flow M...

Page 33: ...re Switch 4 20mA Control Board Cover Safety Switch External Loop Remote 4 20mA Control Leads Connected to Dissolved Ozone Monitor Controller Air Prep Inlet Manual Ozone Output Adjustment Knob Main Power Light External Loop Connector Remote 4 20mA Connector Bonding Ground Lug Power Entry Module OFF ON Switch Cord Input Fuse Carrier Fan and Fan Filter Ozone Outlet Fitting Ozone Output LED s Pressure...

Page 34: ...C5040 High Voltage Drive Board HDO3 I ELPC5042 Description Part LED Display Board HDO3 I ELPC5052 Complete Board Set HDO3 I ELPC5062 High Voltage Transformer HDO3 I ELTR105 Power Supply 48VDC 450w HDO3 II PS450 Power Supply 48VDC 300w HDO3 III PSR822 Drive Module Transformer HDO3 II HDO3 III HVT200 Drive Module Board HDO3 II HDO3 III ELPC5210 4 20mA Control Board HDO3 II HDO3 III ELPC5430 Cooling ...

Page 35: ...sure Relief Valve OXS370 1 Oxygen Concentrator Cover Filter FA40 2 Filter Cooling Fan filter FLT34 1 Filter Inline Particulate Filter ORG10 4 O Ring 2 CD Reaction Chamber Small ORG110 8 O Ring 2 CD Reaction Chamber Large FUS20 5 Fuse Bussmann MDL 5 5 amp 250VAC Slow Blow Main Power FUS66 2 Fuse Littelfuse Minifuse 297003 3 amp 32VAC Drive Board ASPHD30A Maintenance Kit HDO3 III Part QTY Descriptio...

Page 36: ... Shown Electrical Schematic HDO3 I HDO3 II and HDO3 III Line Side Note This system is not dual voltage rated System voltage is 120VAC 60Hz or 220VAC 50Hz Main Power Switch Magnetic Contactor Ozone Generator Dissolved Ozone Monitor Oxygen Concentrator Booster Pump ...

Page 37: ...itch Mother Board 0 VDC 5 VDC 12 VDC 24 VDC 100 VDC Fan Output Control Board LED Display Board High Voltage Board High Voltage Transformer Reaction chamber Manual Ozone Output Control Remote 4 20mA Ozone Output Control External Loop Power Entry Module with Fuses High Voltage Board High Voltage Transformer Reaction chamber Vacuum Switch ...

Page 38: ...er Supply Fan 4 20mA Control Board Remote 4 20mA Ozone Output Control Manual Ozone Output Control External Loop High Voltage Transformer Fuse Fuse Main Power Switch Main Power Light Fan Voltage Selector Switch Vacuum Switch 24 VDC 0 VDC 24VDC Variable Output Signal Reaction Chamber High Voltage Transformer Drive Board Reaction Chamber Drive Board ...

Page 39: ...Module With Fuses Cover Safety Switch Power Supply Power Supply Fan Fan 24VDC 24VDC 24VDC 24VDC Manual Ozone Output Control Remote 4 20mA Ozone Output Control External Loop 4 20mA Control Board Variable Output Signal Drive Board High Voltage Transformer Reaction Chamber Reaction Chamber High Voltage Transformer Drive Board Pressure Switch ...

Page 40: ...39 APPENDIX Section E Drive Board Input Voltage HDO3 II and HDO3 III Shown Dual HO Drive Module ...

Page 41: ...enced with the product and or part must be clearly described The RGA number must appear prominently on the exterior of the shipped box es The product and or part must be packaged either in its original packing material or in comparable and suitable packing material if the original is not available You are responsible for paying shipping charges to CWT and for any damages to the product and or part...

Reviews: