Fleck 7000 Neutralizer Installation & Startup Guide
Page 18
www.cleanwaterstore.com
Rev 120215
8.
Day Override (Display Code DO): Set to 1 to 14 based on your particular filter system requirements. Use the Up
or Down arrows to change the setting. This is the critical setting that allows your filter to backwash every fixed
number of days. See your Installation and Start-up Guide for more information or contact us for suggestions for
this setting. Press the Extra Cycle button.
9.
Regeneration Time: (Display Code RT): Set to 2:00 am generally or sometime when no water is being used, and
no other filter or softener is likely to be in a regeneration cycle. Press the Extra Cycle button.
10.
Regeneration Cycle Step Times: Use this display to set the various minutes of each cycle. Some of the cycles will
be set to 0. Do not set any of the cycles to Off. Use the Up or Down arrows to change the setting to the desired
setting. Press the Extra Cycle button to accept the setting and move to the next parameter.
a.
B1 – Backwash: Set to 8 to 10 minutes.
b.
BD - Brine Draw: Set to 0.
c.
B2 - 2nd Backwash: Set to 0 for most applications.
d.
RR - Rapid Rinse: Set to 6 to 8 minutes
e.
BF - Brine Fill: Set to 0.
f.
SV - Service (meaning it is in Service or filtering mode) no setting is needed for this. Press the Extra
Cycle button
11.
Flow Meter Type (Display Code FM): Set to t1.2 (this is standard Fleck 7000 meter). Press the Extra Cycle button.
12.
Press the Extra Cycle button to save all settings and exit Master Programming Mode. Note that the control
valve may take several minutes to re-home and re-set after the Master Programming steps, do not unplug the
control during this process.