
5.2 Cleaning filter
Notice:
Never use hot water over 104
℉
(40
℃
) to clean the
air filter. Never attempt to operate the unit without
the air filter.
Every time, when filter check LED light, we
suggest to cleaning the filter, it will be better for
healthy, and save energy.
When the AC has not used for a long time, like one
month or more, we suggest to cleaning the filter
before re-use.
6 Troubleshooting
In general, possible trouble is classified in three kinds.
One is called Starting Failure which is caused from an
electrical defect, another is ineffective Air Conditioning
caused by a defect in the refrigeration circuit and
improper application, and the other is called the
Structure Damage.
Problem
Solution
Air conditioner
does not start
Wall plug disconnected. Push plug firmly into wall
outlet.
House fuse blown or circuit breaker tripped.
Replace fuse with time delay type or reset circuit
breaker.
Plug Current Device Tripped. Press the RESET
button.
Control is OFF. Turn Control ON and set to desired
setting.
Air from unit
does not feel
cold enough
Room temperature below 17
℃
(62
℉
). Cooling may
not occur until room temperature rises above
17
℃
(62
℉
).
Temperature sensing element touching cold coil,
located behind air filter. Straighten tube away from
coil.
Reset to a Lower temperature.
Compressor shut-off by changing modes. Wait
approximately 3 minutes and listen for compressor
to restart when set in the COOL mode.
Air conditioner
cooling, but room
is too warm- ice
forming on
cooling coil
behind
decorative front.
Outdoor temperature below 17
℃
(62
℉
). To
defrost the coil, set FAN ONLY mode.
Air filter may be dirty. Clean filter. Refer to Care and
Cleaning section. To defrost, set to FAN ONLY
mode.
Thermostat set too cold for night-time cooling. To
defrost the coil, set to FAN ONLY mode. Then, set
temperature to a Higher setting.
Air conditioner
cooling, but room
is too warm- NO
ice forming on
cooling coil
behind
decorative front.
Dirty air filter- air restricted. Clean air filter. Refer to
Care and Cleaning section.
Temperature is set too High, set temperature to a
Lower setting.
Air directional louvers positioned improperly.
Position louvers for better air distribution.
Front of units is blocked by drapes, blinds, furniture,
etc. - restricts air distribution. Clear blockage in front
of unit.
Doors/ windows/registers, etc. Open- cold air
escapes. Close doors, windows, registers.
Unit recently turned on in hot room. Allow additional
time to remove. Stored heat from walls, ceiling, floor
and furniture.
Air conditioner
turns on and off
rapidly
Dirty air filter- air restricted. Clean air filter
Outside temperature extremely hot. Set FAN speed
to a Higher setting to bring air past cooling coils
more frequently.