23
2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging
cylinder, open the 2-way valve and the 3-way
valve
Connect the charge hose which you
disconnected from the vacuum pump to the
valve at the bottom of the cylinder. If the
refrigerant is R410A, make the cylinder bottom
up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air (be careful of the liquid
refrigerant).
3) Put the charging cylinder onto the electronic
scale and record the weight.
4). Open the valves (Low side) on the charge
set and charge the system with liquid refrigerant
If the system cannot be charge with the
specified amount of refrigerant, or can be
charged with a little at a time (approximately
150g each time) , operating the air conditioner
in the cooling cycle; however, one time is not
sufficient, wait approximately 1 minute and then
repeat the procedure.
5).When the electronic scale displays the
proper weight, disconnect the charge hose from
the 3-way valve’s service port immediately
If the system has been charged with liquid
refrigerant while operating the air conditioner,
turn off the air conditioner before disconnecting
the hose.
6). Mounted the valve stem caps and the
service port. Use torque wrench to tighten the
service port cap to a torque of 18N.m. Be sure
to check for gas leakage.
Summary of Contents for MROHC09AS
Page 14: ...12 5 Wiring Diagram 5 1 Indoor Unit MWOHC09S MWOHC12S MWOHC18S ...
Page 15: ...13 MWOHC24S ...
Page 16: ...14 5 2 Outdoor Unit MROHC09AS MROHC12AS ...
Page 17: ...15 MROHC18AS ...
Page 18: ...16 MROHC24AS MROHC09AS MROHC12AS ...
Page 19: ...17 MROHC18AS ...
Page 29: ...27 T2 7 C 44 6 F the compressor frequency will not be limited ...
Page 53: ...51 Take the 9k model as example P V P U ...
Page 54: ...52 N U P W ...
Page 55: ...53 N W N V ...