X144D e-FlowMeter
Quick Start Programming
SETTINGS – OUTPUT (Continued)
Set Pulse Weight?
NEXT
01.000
Default Pulse Weight is 1.00. Use arrow keys to increase or decrease Pulse Weight.
Flow Rate = Number of Pulses x Pulse Weight / Time. Select
to continue.
NEXT
Set Flow Cutoff
NEXT
030.00
This setting is used to set a minimum flow reading that is displayed on screen before displaying
zero flow. This is used when noise or vibration is causing erratic low flow readings when there is
no flow. Select
to continue.
NEXT
Are you sure you
want to save
changes?
YES
NO
To save changes select
.
To discard changes and advance to next menu select
.
YES
NO
Do you want to test
the 4-20mA Loop?
YES
NO
To test 4 and 20mA outputs select
. To return to settings menu select
.
YES
NO
NEXT
0655
In this menu, a 4mA output signal is generated. To calibrate 4mA output to external device, use
arrow keys to increase or decrease 4mA output. A Digital Multimeter to measure 4mA output.
Select
to continue to 20mA test.
NEXT
EXIT
3273
In this menu, a 20mA output signal is generated. To calibrate 20mA output to external device,
use arrow keys to increase or decrease 20mA output. A Digital Multimeter to measure 20mA out-
put Select
to return to Settings Menu.
EXIT