From Flow Rate or Sensor Frequency screen, select 

to access 

menu. 

 

                 

Settings

X144D e-FlowMeter

Quick Start Programming 

SETTINGS – VALVE (Adjust meter size and valve size parameters)

Note:

Stylus Pen Recommended for Touch Screen Programming

6” 100-01                 v1.0

VALVE

YES

Select 

then 

to configure meter size 

VALVE

YES

Size 1

Size 2

Size 3

Size 4

Select correct METER size from chart below

X144D Sizes

1

2

3

4

Full Port Valve Sizes

2

2-1/2

3

4

6

8

10

12

14

16

18

20

24

30

Reduced Port Valve Sizes

4

4

4

6

8

10

12

14

16

18

20

24 CF CF

YES

Save configuration

SETTINGS – OUTPUT (Adjust Gain, mA Scaling, mA Filtering, Pulse Weight, and 4-20mA Output Test)

OUTPUT

YES

Select 

then 

to configure output. 

OUTPUT

YES

Set the Gain?

NEXT

1.00

Default Gain is 1.00. Use arrow keys to adjust gain to desired value. Increasing or decreasing
value offsets factory calibration. Select 

to continue.

NEXT

Set the 20mA Value?

NEXT

002250.00

Use arrow keys to set 20mA Full Scale Output. Match 20mA value to customer display and/or
SCADA. Select 

to continue.

NEXT

Set Filter Strength

NEXT

4.0

 

width

Default Filter is 4.00. Use arrow keys to increase or decrease filtering of 4-20mA signal. The
higher the average filter strength, the longer the averaging time. Select 

to continue.

NEXT