4 CALIBRATION
4.1
CALIBRATION WITH WATER & WITHOUT CALIBRATION TOOL
Initial situation: The magnet of e-Lift should be within measuring range sensor; The LED should be green before starting
calibration.
1. Activate calibration mode
-
Press button marked
LA
for at least 4 secs. or until the LED starts blinking green.
2. Set 0% closed position
-
Close the valve to reach lowest position.
-
Press button marked
LA
for at least 2 secs. or until the LED appears red.
3. Set 100% open position
-
Open the valve to reach the highest position.
-
Press button marked
LB
for at least 2 secs. or until a solid red LED appears.
If the time taken to fully open the valve from the closed position exceeds 40 seconds, the calibration process times out
and you will need to repeat the process. Please proceed step 1 first then step 3.
4. End calibration mode
- Press
buttons
LA
and
LB
simultaneously (< 1s) to finish calibration and read current value.
Note:
Any of the individual steps for settings can be selected independently. The calibration process can be ended at any time
(step 4).
This mode shows how the valve was calibrated without tools.