Stopping Cycle...

Starting switch opens, solenoid control "A" de-

energizes and shifts, pump continues to run.

High Pressure fluid from the pump is directed

above the diaphragm, applying force to close the

valve.

The valve closes slowly as fluid from the lower

diaphragm chamber is gradually released to

atmosphere through speed control "D" and

solenoid "A". When the valve closes fully, the

limit switch "H" shuts off the pump.

Pump Off...

With pump off, static line pressure is

transmitted through strainer "F", shuttle

valve "C", solenoid control "A", and speed

control "E" to the chamber above the

diaphragm, thus holding the valve closed.

If power failure occurs when valve is open,

the built-in check valve "J" closes

immediately to prevent reverse flow.

Starting Cycle...

Starting switch closes, pump starts, solenoid control

"A" energizes and shifts allowing fluid from upper

diaphragm chamber to drain to atmosphere. High

pressure fluid from pump enters strainer "B" and shifts

shuttle valve "C", which always supplies the highest

pressure from either strainer "B" or "F". High pressure

fluid is transmitted to the lower diaphragm chamber

and opens the valve.The opening speed of the valve is

controlled by speed control "E", which limits the rate

fluid is relieved from above the diaphragm.

Sequence Of Operation

Drain

PT.1

A

D

E H

Enter PT.2

C

B

J

F

Drain

A

E

H

D

Enter

PT.2

PT.1

F

B

C

A

Drain

Enter

C

PT.1

PT.2

E

H

D

F

B

E-60-73 US Units  (R-02/2019)

Optional Electronic Control

The Cla-Val PC-22D provides control of the pump and

pump control valve, preventing surges in the system

when the pump starts or stops. It consists of a pre-wired

electrical  control  panel  employing  a  programmable

valve  controller  to  sequence  the  pump  and  pump

control valve during all modes of operation. Provides

added protection to the pumping system from damage

caused by mechanical, hydraulic or power failure. 

The PC-22D offers all the control features found in the

recommended wiring diagrams for Cla-Val pump control

valves, plus alarms, automatic shutdown and adjustable

timers.

Valve Sizing

Sizing  Model  60-73  Booster  Pump  Control

Valves is similar to sizing non-modulating type

valves. Simply select the smallest size valve that

will handle the pump output at an acceptable

head loss for the application.

Do not oversize.

Oversizing a Booster Pump

Control  Valve  will  nullify  its  ability  to  prevent

surges caused by the starting and/or stopping

of the pump. Maximum flow values are given in

the  selection  table  above.  For  further

information on flow characteristics for this valve,

reference  the  100-30  (60-73)  technical  data

sheet.

Example:

A booster pump station with a rated output of

1000 GPM and 4 psi is an acceptable head loss

for the application. 

Drain Provisions

Each time the valve opens or closes, water is

discharged from the solenoid exhaust port, the

amount varying with the valve size. Provisions

should be made for the disposal of this water.

Exhaust tube must be free of any back pressure.

Provide  an  air  gap  between  the  solenoid

exhaust tube and drain facility.

Model 60-73 Flow Chart 

Uses Basic Valve Model 100-30

12

10

20

30 40

60 80 100

200

500

1000

2000

5000

10,000

      20,000             50,000 

1

2

3

4

6

8

10

20

30

40

60

80

100

5

3

Angle Valve Sizes (Inches)

Globe Valve Sizes (Inches)

6

8

10

24

6

8

16

20

P

re

ss

u

re

 D

ro

p

 —

 p

si

18

14

4

4

Flow Rate

     gpm (water)

Liquid Volume Displaced from Diaphragm Chamber When Valve Opens or Closes

Sizes  (Inches)

2

1

2

"

3"

4"

6"

8"

60-73 

.043gal

.080gal

.169gal

.531gal

1.26gal