CLA-VAL 49-01/649-01 Installation, Operation And Maintanance Manual Download Page 10

Maintenance 

Preventative Maintenance

The Cla-Val Co. Model 100-01 Hytrol Valve requires no lubrication
or packing and a minimum of maintenance. However, a periodic
inspection schedule should be established to determine how the
operating conditions of the system are affecting the valve. The
effect of these actions must be determined by inspection.

Disassembly

Inspection or maintenance can be accomplished without remov-
ing the valve from the line.  Repair kits with new diaphragm and
disc are recommended to be on hand before work begins.

WARNING: 

Maintenance personnel can be injured and equip-

ment damaged if disassembly is attempted with pressure in the
valve. 

SEE CAUTION.

1.

Close upstream and downstream isolation valves 

and inde-

pendent operating pressure when used 

to shut off all pressure

to the valve.

2.

Loosen tube fittings in the pilot system to remove pressure from

valve body and cover chamber. After pressure has been released
from the valve, use care to remove the controls and tubing. Note
and sketch  position of tubing and controls for re-assembly. The
schematic in front of the Technical Manual can be used as a guide
when reassembling pilot system.

3.

Remove cover nuts and remove cover. If the valve has been in

service for any length of time, chances are the cover will have to
be loosened by driving upward along the edge of the cover with a

dull 

cold chisel.

On 6” and smaller valves block and tackle or a power hoist can be
used to lift valve cover by inserting proper size eye bolt in place
of the center cover plug. on 8” and larger valves there are 4 holes
(5/8” — 11 size) where jacking screws and/or eye bolts  may be
inserted for lifting purposes. 

Pull cover straight up 

to keep from

damaging the  integral seat bearing and stem.

4

. Remove the diaphragm and disc assembly from the valve body.

With smaller valves this can be accomplished by hand by 

pulling

straight up on the stem so as not to damage the seat bearing.

On large valves, an eye bolt of proper size can be installed in the
stem and the diaphragm assembly can be then lifted with a block
and tackle or power hoist. Take care not to damage the stem or
bearings.  The valve won't work if these are damaged.

5.

The next item to remove is the stem nut. Examine the stem

threads above the nut for signs of mineral deposits or corrosion.
If the threads are not clean, use a wire brush to remove as much
of the residue as possible. Attach a good fitting wrench to the nut
and give it a sharp “rap” rather than a steady pull. Usually
several blows are sufficient to loosen the nut for further removal.
On the smaller valves, the entire diaphragm assembly can be held
by the stem in a vise 

equipped with soft brass jaws

before

removing the stem nut.

The use of a pipe wrench or a vise without soft brass jaws scars
the fine finish on the stem. No amount of careful dressing can
restore the stem to its original condition. Damage to the finish of
the stem can cause the stem to bind in the bearings and the valve
will not open or close.

6

. After the stem nut has been removed, the diaphragm assembly

breaks down into its component parts. Removal of the disc from
the disc retainer can be a problem if the valve has been in serv-
ice for a long time. Using two screwdrivers inserted along the out-
side edge of the disc usually will accomplish its removal. Care
should be taken to preserve the spacer washers in water, partic-
ularly if no new ones are available for re-assembly.

7.

The only part left in the valve body is the seat which ordinarily

does not require removal. Careful cleaning and polishing of inside
and outside surfaces with 400 wet/dry sandpaper will usually
restore the seat’s sharp edge. If, however, it is badly worn and
replacement is necessary, it can be easily removed.

Seats in valve sizes 1 1/4” through 6” are threaded into the valve
body.  They can be removed with accessory X109 Seat Removing
Tool available from the factory. On 8” and larger valves, the seat
is held in place by flat head machine screws.  Use a tight-fitting,
long shank screwdriver to prevent damage to seat screws. If upon
removal of the screws the seat cannot be lifted out, it will be nec-
essary to use a piece of angle or channel iron with a hole drilled
in the center. Place it across the body so a long stud can be insert-
ed through the  center hole in the seat and the hole in the angle
iron. By tightening the nut a uniform upward force is exerted on
the seat for removal.

NOTE

: Do not lift up on the end of the angle iron as this may force

the integral bearing out of alignment, causing the stem to bind.

VALVE STEM THREAD SIZE

Valve Size       

Thread Size (UNF Internal)

1 1/4"—2 1/2"

10—32

3"—4"

1/4—28

6"—14"

3/8—24

16"

1/2—20

24"

3-12

COVER CENTER PLUG SIZE

Valve Size

Thread Size (NPT)

1 1/4"—1 1/2"

1/4"

2"—3"

1/2"

4"—6"

3/4"

8"—10"

1"

12"

1 1/4"

14"

1 1/2"

16"

2"

24"

4 1/4"

VALVE COVER

DULL COLD CHISEL
(ANGLE UPWARD AS MUCH
AS POSSIBLE)

HAMMER

NUT

ANGLE OR CHANNEL IRON

LONG STUD OR BOLT

NUT OR BOLT HEAD

DO NOT

LIFT

VALVE SEAT

VALVE BODY

4

Distributed By: M&M Control Service, Inc.

                http://www.mmcontrol.com/claval-index.php

800-876-0036     847-356-0566

Summary of Contents for 49-01/649-01

Page 1: ...01 Distributed By M M Control Service INC Phone 800 876 0036 Fax 847 356 0747 Email Sales mmcontrol com Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847...

Page 2: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Page 3: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Page 4: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Page 5: ...um efficiency when mounted in horizontal piping with the cover UP however other positions are acceptable Due to size and weight of cover and internal components of six inch valves and larger installat...

Page 6: ...ng and a minimum of maintenance However a periodic inspection schedule should be established to determine how the fluid handled is affecting the efficiency of the valve assembly 2 Repair and adjustmen...

Page 7: ...tions are acceptable Due to size and weight of the cover and internal components of 8 inch and l arger valves installation with the cover UP is advisable This makes internal parts readily accessible f...

Page 8: ...ng out probable causes and remedies the following three checks can be used to diagnose the nature of the problem before maintenance is started They must be done in the order shown Open Cocks Check ups...

Page 9: ...d The stem should also be checked for scale build up See Maintenance section for procedure 11 For valves 6 and smaller the Hytrol Valve s freedom of move ment check can also be done after all pressure...

Page 10: ...he nut and give it a sharp rap rather than a steady pull Usually several blows are sufficient to loosen the nut for further removal On the smaller valves the entire diaphragm assembly can be held by t...

Page 11: ...mechanically restricting the stroke of the valve The cover must be removed the obstruc tion located and removed See Maintenance Section for procedure Inspection of Parts After the valve has been disa...

Page 12: ...ex Nut 8 and larger 4 Stud 8 and larger 5 Cover Bearing 6 Cover 7 Stem Nut 8 Diaphragm Washer 9 Diaphragm 10 Spacer Washers 11 Disc Guide 12 Disc Retainer 13 Disc 14 Stem 15 Seat 16 Body 17 Spring 22...

Page 13: ...a long life of dependable trouble free operation It s smooth flow passages and fully guided disc and diaphragm assembly assure optimum control when used in piping systems requiring remote control pres...

Page 14: ...e Viton Rubber Parts suffix KB Optional diaphragm disc and o ring fabricated with Viton synthetic rubber Viton is well suited for use with mineral acids salt solutions chlorinated hydrocarbons and pet...

Page 15: ...U S gpm or l s V Fluid Velocity feet per second or meters per second P Pressure Drop in psi or bar CV Factor Formulas for computing C Factor Flow Q and Pressure Drop V P CV Q P CV Q P CV Q P 2 V Funct...

Page 16: ...arger valves installation with cover UP is advisable We recommend isolation valves be installed on inlet and outlet for maintenance Adequate space above and around the valve for service personnel shou...

Page 17: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Page 18: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Page 19: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Page 20: ...r proper reassembly of 21 onto body 18 4 Place lower diaphragm washer 24 o ring 22 diaphragm 12 upper diaphragm washer 11 and belleville washer 20 on yoke extension 17 Screw on diaphragm nut 10 finger...

Page 21: ...g 3 8 NPT Disc Retainer Assy 15 75 psi 30 300 psi Disc Retainer Assy 2 30 psi Yoke Body Seat Assy Seat only 1 4 Bucking Spring Required with 2 30 psi Belleville Washer Powertrol Body O Ring O Ring Dia...

Page 22: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Page 23: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Page 24: ...screw out counterclockwise to decrease flow rate DISASSEMBLY The Differential Control Valve should be removed from the Hytrol Valve assembly Make sure that pressure shutdown is accomplished prior to...

Page 25: ...evidence of cross threading Check inner and outer screens for clogging embedded foreign particles breaks cracks corrosion fatigue and other signs of damage CLEANING After inspection cleaning of the X...

Page 26: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Page 27: ...Check spring for visible distortion cracks and breaks Inspect all parts for damage corrosion and cleanliness CLEANING After disassembly and inspection cleaning of the parts can begin Water service usu...

Page 28: ...r Stamped on Side Description CV Flow Control Part Description Material ITEM DESCRIPTION QUAN 1 Cap SS only 1 2 Nut Jam 1 3 Seat 1 4 Gasket 1 5 Disc 1 6 Spring 1 7 Ring Retaining 1 8 Stem 1 9 O Ring 1...

Page 29: ...Distributed By M M Control Service Inc http www mmcontrol com claval index php 800 876 0036 847 356 0566...

Page 30: ...screen stock number 68373A All other parts available only in replacement assembly Standard 60 mesh pilot system strainer for fluid service PL X43 R 6 00 PARTS LIST Distributed By M M Control Service I...

Page 31: ...of the inlet flange These two brass plates appear on 3 8 1 2 and 3 4 size valves and are located on the valve cover These two brass plates appear on 1 through 3 size screwed valves or 1 through 2 flan...

Page 32: ...any of the foregoing or assume any additional liability or responsibility in connection with the product The liability of Cla Val is limited to material replacements F O B Newport Beach California TE...

Page 33: ...01D 9817902B N A 9817903K 9817905E 9817905E 3 8 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 6 8 9169806J 9169807G 9169808E 9169809C 9169810A 9169817F 9169818D 9169819B 9169820K N A N A N A N A N A N A N A 91698...

Page 34: ...Cl CFC2 C1 CSM 11 A2 2 CSM 11 A2 2 33A 1 33A 2 Pilot Assembly Only Complete Float Control less Ball Rod Disc Distributor Seals Mechanical Parts Assy Pilot Assembly Only Complete Internal Assembly Seal...

Reviews: