Static calibration can create low and high pressure points for the 4 and 20 milliamp signals without rotating the actuator.

1) Determine high and low pressure that corresponds to the 4-20 mA signals.

2) Open the "Static Calibration" mode. 

3) Use existing system pressure as a reference point or change using the increase.

4) Once desired reference setting is attained, consult spring chart to obtain pressure change per pilot revolution.

5) Calculate the number of turns between the reference pressure and the low and high values.

6) Enter these numbers into the "Turn to low and to high points". Numbers must be positive and can contain up to 

decimal points.

7) Click "Download Calibration" button to complete actuator setup.

8) Click cancel button to restart calibration.

Example: 

Required pressure range for 4-20 mA signals is 55 to 95 psi and system pressure is 70 psi. The 20-105 CRD-32 is
13 psi per turn. Therefore, 95 minus 55 divided by 13 = 1.92 turns is entered into the high point window. For the
low point settings: 70 minus 55 = 1.15 turns which is entered into the low point window.
(Remember to click "Download Calibration" button).

Spring Chart - PSI change per complete pilot revolution

CRD

15 -75 = 10.2 psi per turn

CRD

2-105 = 13

psi per turn

CRD 30-300 = 29

psi per turn

Static Calibration

Fig. 5

Page 7

Summary of Contents for 130VC-2

Page 1: ...r use Consult Cla Val factory technical support if you have questions C The five wire cable is permanently attached to 130VC 2 actuator and should be terminated in suitable junction box for all field...

Page 2: ...uter for installa tion at a later time click SAVE to save this program 3 This program will automatically be installed in new e Drive folder in C Program Files Cla Val folder on your computer A new Cla...

Page 3: ...ctuator has power it will do one of the following Go to 4 mA Actuator will decrease pilot setting to 4 mA position Last position Actuator will stay in last position Highly recommended Go to 20 mA Actu...

Page 4: ...an orifice plate a calibrated differential pressure gauge or transmitter is recommended 3 Once desired low pressure or flow is reached and actuator is topped click Low point setting button 4 Look at p...

Page 5: ...Look at pressure gauge or flow sensor and use Increase actuator or Decrease actuator buttons to increase pressure or flow as close as is practical to desired HIGH pressure point 3 Enter this value in...

Page 6: ...red LOW pressure point 3 Enter this value in the projected Low point calibration window 4 Next click on Low point setting button and then click on Download calibration button The actuator automaticall...

Page 7: ...s into the Turn to low and to high points Numbers must be positive and can contain up to decimal points 7 Click Download Calibration button to complete actuator setup 8 Click cancel button to restart...

Page 8: ...ween high and low starting points Accuracy of projected values is based on accuracy of initial value and any error will be magnified when projected from starting point Why is actuator LED still blinki...

Reviews: