      Cisco uBR10-SRP-OC12SML DPT WAN Line Card for the Cisco uBR10012 Router

About Removing and Replacing a Cisco uBR10-SRP-OC12SML DPT WAN Line Card

15

Cisco uBR10-SRP-OC12SML DPT WAN Line Card

78-13602-01

About Removing and Replacing a 
Cisco uBR10-SRP-OC12SML DPT WAN Line Card

Use the following procedure to install a new Cisco uBR10-SRP- OC12SML DPT WAN line card or to 
replace an existing line card. If two line cards are installed for redundant operation, you can remove one 
card and replace it without interrupting system operations. 

Warning

Warning Because invisible radiation may be emitted from the aperture of the port when no fiber 
cable is connected, avoid exposure to radiation and do not stare into open apertures. 

Tools and Parts Required

To remove and replace an individual Cisco uBR10-SRP- OC12SML DPT WAN line card you need the 
following:

Replacement Cisco uBR10-SRP- OC12SML DPT WAN line card, product order number 
UBR-1OC12/P-SML=.

ESD-preventive wrist strap.

Anti-static surface.

Screwdriver (number 2 Phillips head recommended).

Unpacking the Cisco uBR10-SRP-OC12SML DPT WAN Line Card 

To unpack the line card complete the following steps:

Caution

Make sure you are properly grounded with an ESD preventative ground strap. 

Step 1

Open the shipping box.

Step 2

Remove the Cisco uBR10-SRP- OC12SML DPT WAN line card from the box.

Step 3

Place the Cisco uBR10-SRP- OC12SML DPT WAN line card on an anti-static surface.

.

Summary of Contents for uBR10-SRP-OC12SML

Page 1: ...nd Warnings page 8 About Removing and Replacing a Cisco uBR10 SRP OC12SML DPT WAN Line Card page 15 About Troubleshooting the Cisco uBR10 SRP OC12SML DPT WAN Line Card page 21 Technical Specifications page 22 Obtaining Documentation page 23 Obtaining Technical Assistance page 24 Note Before using this product see the translations for these warnings and other warnings that apply to this product in ...

Page 2: ...ine card requires two card slots For that reason the card is normally installed in Slot 2 and Slot 4 if you are using two cards If you are using only one card than install the card in Slot 2 Slot 3 or Slot 4 See Figure 1 Attenuation The Cisco uBR10 SRP OC12SML DPT WAN line card is designed to be used at any distance between 15 and 40 kilometers km For shorter distance operations less than 15 km us...

Page 3: ...3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0...

Page 4: ...12SML DPT WAN line card Figure 2 Cisco uBR10 SRP OC12SML DPT WAN Line Card The part number of the card UBR10 SRP OC12SML is next to the CLEI code label The label 2xOC 12 STM 4 SRP SM LR above the transmit and receive port connections defines the optical carrier specifications for this card Figure 3 Cisco uBR10 SRP OC12SML DPT FacePlate 68500 Ejector Lever Ejector Lever CLEI code Captive screws 4 6...

Page 5: ...SML DPT WAN line card can be hot swapped RX CARRIER B Green Off Indicates that the DPT port WAN has detected valid SONET or SDH framing on the received carrier No valid SONET or SDH framing ACTIVE Green Off Indicates that side B of the DPT port line is functioning Not active RX PKTS Packets Blinking Green Off Indicates that the DPT port line has received a packet This LED flickers in normal operat...

Page 6: ...re not available from Cisco Systems For SONET or SDH single mode fiber optic connections use one duplex SC type connector Figure 4 or two simplex SC type connectors See Figure 5 Figure 4 Duplex SC Cable Connector Figure 5 Simplex SC Cable Connector You can use either a duplex fiber cable or two simplex fiber cables between the DPT port line and the device to which the DPT port line is connected If...

Page 7: ...r the Cisco uBR10012 Router Connectors and Cables 7 Cisco uBR10 SRP OC12SML DPT WAN Line Card 78 13602 01 Figure 6 Attaching the Attenuator and Duplex Fiber Optic Cables to the WAN Line Card 62703 Symplex cable Attenuator Attenuators Duplex cable ...

Page 8: ...aroitusmerkki merkitsee vaaraa Olet tilanteessa joka voi johtaa ruumiinvammaan Ennen kuin työskentelet minkään laitteiston parissa ota selvää sähkökytkentöihin liittyvistä vaaroista ja tavanomaisista onnettomuuksien ehkäisykeinoista Tässä julkaisussa esiintyvien varoitusten käännökset löydät kyseessä olevaa Cisco asennuspohjaa koskevasta säännösten noudattamista ja turvallisuustietoja koskevasta a...

Page 9: ...s com circuitos eléctricos e com quaisquer práticas comuns que possam prevenir possíveis acidentes Para ver as traduções dos avisos que constam deste manual consulte o documento acerca dos Regulamentos e Informação de Segurança apropriado fornecido com o produto Cisco Advertencia Este símbolo de aviso significa peligro Existe riesgo para su integridad física Antes de manipular cualquier equipo con...

Page 10: ...c shock use caution when working near WAN ports When detaching cables detach the end away from the router first Waarschuwing Er is gevaarlijke netwerkspanning aanwezig in WAN poorten ongeacht of de stroom naar de router INGESCHAKELD of UITGESCHAKELD is Om elektrische schokken te vermijden dient u voorzichtig te werk te gaan wanneer u in de nabijheid van WAN poorten werkt Wanneer u kabels losmaakt ...

Page 11: ...ligada OFF Para evitar choques eléctricos tenha o devido cuidado ao trabalhar perto das portas WAN Ao desconectar os cabos separe primeiro a extremidade que se encontra ligada ao dispositivo repartidor de mensagens Advertencia Hay tensiones de red peligrosas en los puertos de redes de área extendida WAN tanto con la alimentación al router conectada como desconectada Para evitar la sacudida eléctri...

Page 12: ...ent for Sweden Advertencia Producto láser Clase I Varning Laserprodukt av klass 1 Varoitus Alleviates ja suojalukitus ohitettaessa olet alttiina näkymättömälle lasersäteilylle Äjä katso säteeseen Warning Invisible laser radiation when this component is opened and the preregulation is disabled Do not look into the laser beam Varning Osynlig laserstrålning när denna del är öppen och förregleringen ä...

Page 13: ...er Warnung Aus der Öffnung des Ports kann unsichtbare Laserstrahlung austreten wenn kein Kabel angeschlossen ist Kontakt mit Laserstrahlung vermeiden und nicht in offene Öffnungen blicken Avvertenza Poiché quando nessun cavo è collegato alla porta da quest ultima potrebbe essere emessa radiazione laser invisibile evitare l esposizione a tale radiazione e non fissare con gli occhi porte a cui non s...

Page 14: ...e or intermittent failures The AC input power shelf and its AC power modules contain a printed circuit card that is fixed in a metal carrier Electromagnetic interference EMI shielding and connectors are integral components of the carrier Although the metal carrier helps to protect the cards from ESD use an antistatic strap each time you handle the modules Following are guidelines for preventing ES...

Page 15: ...rture of the port when no fiber cable is connected avoid exposure to radiation and do not stare into open apertures Tools and Parts Required To remove and replace an individual Cisco uBR10 SRP OC12SML DPT WAN line card you need the following Replacement Cisco uBR10 SRP OC12SML DPT WAN line card product order number UBR 1OC12 P SML ESD preventive wrist strap Anti static surface Screwdriver number 2...

Page 16: ...uBR10 SRP OC12SML DPT WAN Line Card Captive Screws 67821 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U...

Page 17: ...C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR...

Page 18: ... cover must always be installed in a blank Cisco uBR10 SRP OC12SML DPT WAN line card slot The product order number for the blank Cisco uBR10 SRP OC12SML DPT WAN line card cover is ESR LC COVER 67819 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR...

Page 19: ...the chassis so that it firmly seats in the backplane connectors Step 4 To secure the line card in the chassis simultaneously close the ejector levers 67820 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U S 2 U S 0 U S 1 U S 2 U S 3 D S 0 uBR MC28C EN AB LE D U S 1 D S 1 U S 0 U S 3 U...

Page 20: ... its power on self test The Maintenance LED stays on briefly about 5 to 6 seconds and then shuts off If the Maintenance LED remains on or is flashing see About Troubleshooting the Cisco uBR10 SRP OC12SML DPT WAN Line Card For short distances less than 15 km an attenuator must be added to the cable configuration for the Cisco BR10 SRP OC12SML DPT WAN line card See Technical Specifications page 22 S...

Page 21: ... of the chassis check for bent pins on the backplane If there are bent pins contact TAC for instructions Step 2 Verify that the PRE modules are operating properly The Status LED is on green The Fail LED is off No Alarm LED s are on yellow Step 3 If both PREs are operating correctly check the Power LEDs on each uBR10 SRP OC12SML DPT WAN line card Are the Power LEDs on each line card on green If no ...

Page 22: ... 40 W 136 5 btu1 1 British Thermal Units MTBF 153 624 hours Temperature range Operating 41 to 104 F 5 to 40 C Storage 40 to 158 F 40 to 70 C Relative humidity Operating 5 to 85 Storage 5 to 95 Operating altitude 197 to 13 123 ft 60 to 4000 m Receiver sensitivity Ptyp 29 0 dBm Pmin 31 dBm Pmax 7 dBm Transmitter output power Ptyp 1 0 dBm Pmin 3 dBm Pmax 2 dBm Other information The maximum distance o...

Page 23: ...tional information see the monthly What s New in Cisco Product Documentation which also lists all new and revised Cisco technical documentation at http www cisco com en US docs general whatsnew whatsnew html Subscribe to the What s New in Cisco Product Documentation as a Really Simple Syndication RSS feed and set content to be delivered directly to your desktop using a reader application The RSS f...

Page 24: ...elength Router and WebViewer are trademarks of Cisco Systems Inc Changing the Way We Work Live Play and Learn Discover All That s Possible and Empowering the Internet Generation are service marks of Cisco Systems Inc and Aironet ASIST BPX Catalyst Cisco the Cisco Certified Internetwork Expert logo Cisco IOS the Cisco IOS logo Cisco Systems Cisco Systems Capital the Cisco Systems logo Enterprise So...