Chapter 4 Installation and Maintenance
Installing the SCE 2000 Platform
Site Requirements
and
contain the site requirement specifications for the SCE 2000.
*Short term is defined as not more than 96 consecutive hours, not more than 15 days in one year. 360
hours total in any given year, but no more than 15 occurrences in a one-year period.
For more complete information regarding safety and regulatory compliance, refer to the
Compliance and Safety Information for the Cisco Service Control Engine
document.
The DC-powered SCE 2000 should be installed in a Restricted Access Location only.
Installing the SCE 2000 Platform
The SCE 2000 operates as either a tabletop or a rack-mounted unit. A rack-mounting kit is included with
the SCE 2000 when it is shipped from the factory. The kit provides the hardware needed (see
) to mount the SCE 2000 in either of two types of standard 19-inch equipment
rack:
•
19-inch rack with only two posts in the front — Use the supporting brackets included in the kit
•
19-inch rack with four posts, two in the front and two in the back — Use the crossrail supports
included in the kit
If you are not rack-mounting your SCE 2000 , place it on a sturdy tabletop or workbench. A rubber feet
kit is included for tabletop installations.
Table 4-2
SCE 2000 Climate Requirements
Specification
Acceptable Range
Temperature -
nominal 41°F to 104°F (5°C to 40°C)
Short term temperatures*
23°F to 131°F (-5°C to +55°C)
Relative humidity
5% to 95% (non-condensing)
Heat dissipation
683 BTU/hour
Table 4-3
SCE 2000 EMC and Safety
Approval
Specification
EMC
•
CE Mark
•
EMISSIONS: FCC Part 15 CFR 47 Class A, EN 55022 Class A, CISPR22
Class A, VCCI Class A, AS/NZS CISPR22 Class A
•
Immunity - EN 50082-1 EN 55024, CISPR24 (ESD, RFI, EFT, etc.)
(Commercial)
Safety
UL/CSA 60950, IEC60950, EN60950, AS/NZS, 60950,
NOM-019,IEC/EN60825-1, -2, 21CFR1040, 73/23/ECC