C H A P T E R
2
Preparing the Site
•
Temperature Requirements, page 5
•
•
•
Dust and Particulate Requirements, page 6
•
Minimizing Electromagnetic and Radio Frequency Interference, page 6
•
Shock and Vibration Requirements, page 7
•
Grounding Requirements, page 7
•
Planning for Power Requirements, page 7
•
•
Rack and Cabinet Requirements, page 9
•
Clearance Requirements, page 10
Temperature Requirements
The switch requires an operating temperature of 32 to 104 degrees Fahrenheit (0 to 40 degrees Celsius). If
the switch is not operating, the temperature must be between
–
40 to 158 degrees Fahrenheit (
–
40 to 70 degrees
Celsius).
Humidity Requirements
High humidity can cause moisture to enter the switch. Moisture can cause corrosion of internal components
and degradation of properties such as electrical resistance, thermal conductivity, physical strength, and size.
The switch is rated to withstand from 5- to 95-percent (non-condensing) relative humidity.
Buildings in which the climate is controlled by air-conditioning in the warmer months and by heat during the
colder months usually maintain an acceptable level of humidity for the switch equipment. However, if the
switch is located in an unusually humid location, you should use a dehumidifier to maintain the humidity
within an acceptable range.
Cisco Nexus 93108TC-FX ACI Mode Hardware Installation Guide
5
Summary of Contents for Nexus 93108TC-FX
Page 6: ...Cisco Nexus 93108TC FX ACI Mode Hardware Installation Guide vi Contents ...
Page 14: ...Cisco Nexus 93108TC FX ACI Mode Hardware Installation Guide 4 Overview Overview ...
Page 65: ...Cisco Nexus 93108TC FX ACI Mode Hardware Installation Guide 55 LEDs Power Supply LEDs ...
Page 66: ...Cisco Nexus 93108TC FX ACI Mode Hardware Installation Guide 56 LEDs Power Supply LEDs ...