C H A P T E R
2
Installing and Removing Power Components
This chapter provides instructions on how to install and remove Cisco CRS Carrier Routing System 16-Slot
line card chassis power components.
This chapter presents the following topics:
•
Power Component Information Common to the Two Types of Power Systems
•
Installing and Remove Fixed Configuration Power Components
•
Installing and Removing Modular Configuration Power Components
•
Converting a Chassis from Fixed Configuration Power to Modular Configuration Power
•
Power Systems Overview, on page 15
•
Power Component Information Common to the Two Types of Power Systems, on page 16
•
Installing and Remove Fixed Configuration Power Components , on page 29
•
Installing and Removing Modular Configuration Power Components, on page 57
•
Converting a Chassis from Fixed Configuration Power to Modular Configuration Power , on page 96
Power Systems Overview
There are two options for power systems: the fixed configuration power system and the modular configuration
power system. Power components are not interchangeable between the fixed and modular configuration power
system.
•
Fixed configuration power system
Consists of two power shelves, DC power entry modules (PEMs) or AC rectifiers, and alarm modules. It is
available in versions for DC and AC power supplies. The AC version requires either 3-phase AC-Delta or
3-phase AC-Wye input power to the power shelves. It provides power sharing across power zones. The fixed
configuration power system includes SNMP MIBS and XML support.
•
Modular configuration power system
Consists of two power shelves, AC or DC power modules (PMs), and alarm modules. It is available in versions
for DC and AC power supplies. However, unlike the fixed configuration power system, the AC version of
the modular configuration power system requires single-phase AC input power to the power shelves; there is
no 3-phase AC-Wye or AC-Delta. If you have 3-phase AC Delta or AC Wye at your equipment, a
Cisco CRS
power distribution unit (PDU)
will be required to convert 3-phase AC input power to single-phase AC input
power for the power shelf. At the shelf level, the power system provides 2N redundancy; the PMs themselves
Cisco CRS Routers 16-Slot Line Card Chassis Installation Guide
15