Value
Description
Power Redundancy (2N)
2N: Requires 6 “A” battery plant feeds and 6 “B” battery plant
feeds (up to 12 total)
DC
2N: Requires two independent 3-phase AC sources
AC, 3-phase
DC Input
–48 VDC North America–60 VDC European
Community(range –42 to –75 VDC)
Nominal input voltage
50 A max at –48 VDC40 A max at –60 VDC
Input current
3W+PE (3 wire + protective earthing
)
AC Input, Delta 3-phase
3-phase 200 to 240 VAC, phase-to-phase(range 180 to 264
VAC, phase-to-phase)
Nominal input voltage
50/60 Hz (range 47 to 63 Hz)
Nominal line frequency
60 A
Recommended AC service
3W+N+PE (3 wire + n protective earthing1)
AC Input, Wye 3-phase
3-phase 200-240/346-415 VAC(range 180 to 264 VAC,
phase-to-neutral)(range 311 to 456 VAC, phase-to-phase)
Nominal input voltage
50/60 Hz (range 47 to 63 Hz)
Nominal line frequency
40 A (North America)32 A (International)
Recommended AC service
1
Protective earthing conductor (ground wire).
Modular Configuration Power Specifications
The table lists the modular configuration power specifications for Cisco CRS 16-Slot Line Card Chassis.
Table 9: Line Card Chassis Modular Configuration Power Specifications
Value
Description
2 AC or 2 DC power shelves (Cannot mix AC and DC power
shelves.)
Power shelves
Supports up to 8 DC power modules (PMs) 6 PMs are shipped
per shelf
DC power shelf
Supports up to 6 DC power modules (PMs) 5 PMs are shipped
per shelf
AC power shelf
Cisco CRS Routers 16-Slot Line Card Chassis Installation Guide
236
Technical Specifications
Modular Configuration Power Specifications