Figure 15: DC Power Supply Terminal Block Ground Cable Lugs
This illustration shows the DC power supply for the Cisco Catalyst 9800-80 Wireless Controller.
Note
Step 5
For easier cable-management, insert the negative lead cable first.
Replace the ground lug with a cable in the following order:
• Wire terminal
• Screw with captive washer
Step 6
Tighten the M3 Screw with captive washer to recommended torque of 5 in-lbs for the positive stud and wire.
Secure the wires coming in from the terminal block so that casual contact does not disturb the wire connections.
Note
Cisco Catalyst 9800-80 Wireless Controller Hardware Installation Guide
81
Removing and Replacing FRUs
Wiring the DC Input Power Source