15
2.4
Free Access Underfloor Connection of Power Cable
If the height of underfloor is less than 300mm (11.8 in.), the power distribution is set to sideways.
FIGURE 2.10 When Underfloor Height is less than 300mm (11.8 in)
Number
Description
(1)
Free access floor
(2)
Less than 300mm (11.8 in)
(3)
Recipient power distribution
The connector format and cable bend radius of power cable are considered at the time of connecting the
power cable of power distribution box (or base cabinet) under the free access floor. It is recommended that
the under floor height is 300 mm (11.8 in) or more.
The recipient power distribution should be arranged near the device.
FIGURE 2.11 When the under floor height is 300 mm (11.8 in) or more.
Number
Description
(1)
Free access floor
(2)
200 mm (9.8 in)
(3)
300 mm (11.8 in) or more
(4)
Recipient power distribution
Remarks
The above figure shows an example of 19-inch rack mounted with the device.
2.5
Cutoff Characteristics of Distribution Panel (At the time
of connecting power distribution box)
At the time of connecting the distribution panel through power distribution box, protection should be
coordinated so that the breaker of the device (or power distribution box) trips before the breaker of the
distribution panel trips. Such protection should be maintained. Therefore, the distribution panel should have
the characteristic conditions shown in “
TABLE 2.3 Characteristic Condition of Distribution Panel Breaker
”.