Appendix A Cisco ASR 14000 Series 8-Slot Line Card Chassis Specifications
The following table lists the environmental specifications for the Cisco ASR 14000 series 8-slot line card
chassis.
AC (Delta or Wye 3-phase)
2N (two independent Delta or Wye 3-phase power
sources required)
DC Input
Nominal input voltage
–48 VDC North America
–54 VDC Telco (RBOC)
–60 VDC International
(range –40.5 to –75 VDC)
Input current
(PDU rated for 60 A)
56 A (nominal)
66 A at –40.5 VDC (maximum)
AC Input, Delta 3-phase
3W + PE
Input voltage
3-phase 200 to 240 VAC (nominal)
(range 170 to 264 VAC, phase-to-phase)
Line frequency
50 to 60 Hz
(range 47 to 63 Hz)
Recommended AC service
(PDU rated for 24 A)
30 A
AC Input, Wye 3-phase
3W + N + PE
Input voltage
3-phase 200 to 240 VAC (nominal)
(range 170 to 264 VAC, phase-to-neutral)
(range 295 to 457 VAC, phase-to-phase)
Line frequency
50 to 60 Hz (nominal)
(range 47 to 63 Hz)
Recommended AC service
(PDU rated for 14 A)
16 A International
20 A North America
Table A-1
Cisco ASR 14000 Series 8-Slot Line Card Chassis Component and Power
Specifications (continued)
Table A-2
Cisco ASR 14000 Series 8-Slot Line Card Chassis Environmental Specifications
Description
Value
Temperature
Operating, nominal: 41° to 104°F (5° to 40°C)
Operating, short-term: 23° to 122°F (–5° to 50°C)
Nonoperating: –40° to 158°F (–40° to 70°C)
Humidity
Operating: 5 to 85% noncondensing
Nonoperating: 5 to 90% noncondensing, short-term operation
Altitude
1 to 5,906 ft (-60 to 1,800 m) at 122°F (50°C), short-term
Up to 13,123 ft (4,000 m) at 104°F (40°C) or below
Heat dissipation
27,350 BTUs/hr
External cooling
requirements
2.3 tons
Acoustic noise
74 dB at 3.28 ft. (1 meter) in front of chassis
(nominal reading at room temperature)