The following shows all the lead wires installed.
Figure 34: Cisco +24 VDC Power Supply Terminal Block With Lead Wires Installed
Ground lead wire
3
Positive lead wire
1
—
—
Negative lead wire
2
Make sure the stripped end of each lead wire is twisted tightly together. This makes insertion easier. Then make
certain the entire lead wire is inserted all the way into its receptacle. If any exposed wire at the stripped end of
a lead is visible after inserting the lead into its receptacle, remove the lead from the receptacle, use the wire
stripper to cut the stripped end of the lead, and then reinsert.
Note
When securing the ground, positive, and ne24 VDC-input leads to the power supply faceplate, leave
extra service loop in the ground (GND) lead to ensure that the ground lead is the last lead wire to disconnect
from the power supply if a great deal of strain is placed on all three leads.
Caution
Cisco ASR 1000 Series Router Hardware Installation Guide
52
Cisco ASR 1002 Router Overview and Installation
Connecting Cisco 24 VDC Power Supply