Cisco 6100 Thermal Upgrade Kit Installation Procedures
78-10158-01
Installing the Cisco 6100 Thermal Upgrade Kit
Attach Cisco 6100 Power Connections for a Single-Power Feed
Complete the following steps to attach the Cisco 6100 power connections (P13) to the fuse and alarm
panel for a single-power feed:
Caution
Do not reuse the wire you removed in the “Disconnect the Cisco 6100 Power Connections”
section on page 15, unless it is 12 AWG or larger.
Step 1
Measure enough wire (12 AWG black and red copper solid or stranded wire) to connect each of the
Cisco 6100 power connections to the fuse and alarm panel.
Figure 14 shows the Cisco 6100 power connections wired to the fuse and alarm panel for a
single-power feed.
Figure 14
Power Connections for the Cisco 6100—Single-Power Feed
Step 2
Use a wire stripper to remove the casing from both ends of the wires.
Step 3
Use a Phillips-head screwdriver, to attach a wire to the –48V_A power input connection on the
Cisco 6100 (P13).
Step 4
Loop the wire through the ferrite as shown in Figure 15.
Figure 15
Wire Looped through Ferrite
1 2 3 4 5 6 7 8 9 10
Cisco 6130
P13
-48V_A
-48RTN
-48V_B
-48RTN
NEG
NEG
POS
POS
NEG DC
NEG DC
POS RTN
POS RTN
B
A
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
18394
18375
Ferrite