7.- TECHNICAL FEATURES
Power supply
Rated voltage
24 V ± 10%
Consumption
STM-S12, STM-S24
3.6 W
STM-H6
2.3 W
STM-H10
2.1 W
STM-H20
3.3 W
Installation category
CAT II 150 V
Voltage measurement circuit
Voltage measurement margin
- 25... - 1500 V
Input impedance
2400 kΩ
Min� voltage measurement (Vstart)
- 25 V
Max� consumption of the voltage input
0.625 mA
Installation category
CAT II 1500 V
Current measurement circuit
(STM-S12 and STM-S24 Models)
Channels
STM-S12
STM-S24
12
24
Current measurement margin
0.1 ... 45 A
0.1 ... 30 A
Min� current measurement (Istart)
0.1 A
Input impedance
0.5 mΩ
Max� consumption of the current input
1.0125 W per channel
Installation category
CAT II 1500 V
Current measurement circuit (STM-H6, STM-H10 and STM-H20 Models)
Channels
STM-H6
STM-H10
STM-H20
6
10
20
Current measurement margin
0.1 ... 100 A
0.1 ... 50 A
0.1 ... 50 A
Min� current measurement (Istart)
0.1 A
Installation category
CAT II 1500 V
Accuracy
Voltage measurement
± 1% of full scale
Current measurement
STM-S12, STM-S24
± 1% of full scale
STM-H6, STM-H10,
STM-H20
± 2% of full scale
Digital inputs
Quantity
3
Type
Potential free contact
Insulation
Optoisolated
Maximum short-circuit current
32 mA
Maximum open circuit voltage
24 V
Pt100 input
Range
- 30... 100 ºC
Resolution
± 0.1 mA
Accuracy
± 3ºC
Summary of Contents for STM-H10
Page 2: ...2 STM S12 STM S24 STM H6 STM H10 STM H20 Instruction Manual...
Page 37: ...37 Instruction Manual STM S12 STM S24 STM H6 STM H10 STM H20...
Page 39: ...39 Instruction Manual STM S12 STM S24 STM H6 STM H10 STM H20 10 EU DECLARATION OF CONFORMITY...
Page 40: ...40 STM S12 STM S24 STM H6 STM H10 STM H20 Instruction Manual...
Page 41: ...41 Instruction Manual STM S12 STM S24 STM H6 STM H10 STM H20...