20
RECmax Lpd
Instruction Manual
mA
I n
REC
PROG
N
Figure 10: Screens after an earth leakage protection trip�
If the trip is caused by a fault in the protection due to overloads or a short circuit, a screen will ap-
pear indicating the number of reclosing attempts carried out by the circuit breaker. (See
“5.2.2.- CIRCUIT BREAKER TRIP”
REC
N
Figure 11: Screen after a circuit breaker trip�
After an automatic reclosing sequence, the partial reclosing meters restart after 15
or 30 minutes after the last reclose, according to the value configured (see “
SDR: EARTH LEAKAGE RECLOSING SEQUENCE”
and
)
4�10�2�- AUTOMATIC RECLOSING IS NOT POSSIBLE
Automatic reclosing may not be possible for one of the following reasons:
1�-
Reclosing has been disabled when programming the device. The display will show the cause
of the trip without the
REC
symbol.
The reset is only possible by modifying the Configuration of the device, see
AND
“6.2.2.- SRM: CIRCUIT BREAKER RECLOSING SEQUENCE”
2�-
The number of reclosing attempts has been exhausted. The display will show the cause of
the trip without the
REC
symbol.
In this case, the reset is only possible by pressing the
RESET
key or by an external order of the
EXT
input.
Reclosing the device with the
RESET
key or the
EXT
input restarts the partial reclosing meters.
3�-
The device was tripped manually by pressing the
TEST
key.
The display will show the “
TEST
”
text, see
“5.2.3.- TRIPPING WITH THE TEST KEY”
�
In this case, the reset is only possible by pressing the
TEST
key again.
4�-
The trip was caused by the
EXT
remote control input. The display will show the “
EXT
” text,
see
“5.2.4.- TRIP DUE TO EXT ON/OFF INPUT”
In this case, reclosing is only possible with another external order of the
EXT
remote control
input.