22
RECmax-CVM
Instruction Manual
4�6�-
INPUTS
The
RECmax-CVM
has two keys:
EXT ON/OFF
input
) enables the remote control of the main
switch, trip or reset of the switch depending on its status�
EXT LOCKED
locking input
) allows you to disable the reset�
Table 9: Inputs�
Inputs
Type
Activation mode
EXT ON/OFF
Voltage-free
200 ms pulses
EXT LOCKED
Voltage-free
By level
4�7�- OUTPUTS
The
RECmax-CVM
has four outputs:
REC LOCKED locking alarm
(terminals 13 and 14 in
) indicates that the device is locked,
i�e� that it cannot be automatically reclosed and needs a manual or external reset to recover its
normal operation�
Table 10: REC LOCKED locking alarm�
Automatic
reclosing
REC LOCKED locking alarm
Contact 9 - 10
Open
X
Closed
Note:
The
REC LOCKED locking alarm
has the
Positive safety
Configuration; loss of power is
treated as an alarm. This type of operation can be configured, see
If configured
without positive safety
and the device loses power, the device
may be locked and the
REC LOCKED
output won't be activated�
POSITIVE SAFE OUTPUT fault alarm
) indicates whether there
is any power or not�
Table 11: POSITIVE SAFE OUTPUT fault alarm�
Power supply
POSITIVE SAFE OUTPUT fault alarm
Contact 14 - 15
Closed
X
Open