RECmax-CVM
Instruction Manual
Press the
PROG
key to save the selected sequence and exit the setup menu; when exiting, the screen
in
is displayed for a few seconds�
If you do not press any key for 10 s, the screen shown in
appears and the device opens the
Delay and Sensitivity
screen, without saving the changes made�
If
SRM
and
SRD
have been configured with the number 0 sequence, automatic reclos-
ing will be fully disabled� The
REC
symbol disappears from the display�
Default value: MA 5
6�2�3�- RSTC: PARTIAL METER RESETTING
The partial reclosing meters are reset on this screen�
PROG
PROG
PROG
Press the
RESET
key to move between the different options:
NO
, the meters are not reset�
YES
, the meters are reset�
Press the
PROG
key to save the selected option and exit the setup menu; when exiting, the screen in
is displayed for a few seconds�
If you do not press any key for 10 s, the screen shown in
appears and the device opens the
Delay and Sensitivity
screen, without saving the changes made�
In this section only the partial meters are set to zero, i�e�, those that separately accu-
mulate the no� of recloses caused by a circuit breaker trip (MA) or by an earth leakage
trip (DI)� See
"6.2.6.- FACT: FACTORY CONFIGURATION”
to reset the total meter�
Default value: NO
6�2�4�- POLT: CONFIGURATION OF REC LOCKED OUTPUT
Configure the type of contact of the
REC LOCKED
output on this screen�
PROG
PROG
PROG
Press the
RESET
key to move between the different options: