7.- TECHNICAL FEATURES
AC Power supply
(4)
Rated voltage
80 ... 270 V ~
Frequency
50 / 60 Hz
Consumption
2.7 ... 5 VA
Installation category
CAT III 300 V
DC Power supply
(4)
Rated voltage
80 ... 270 V
18 ... 36 V
Consumption
1.5 ... 1.6 W
1.2 W
Installation category
CAT III 300 V
(4)
Depending on model :
DHC-96 mAdc
Model
Power supply
80 ��� 270 V ~
80 ��� 270 V 18 ��� 36 V
M22368
-
M223680030000
-
-
DHC-96 Adc
Model
Power supply
80 ��� 270 V ~
80 ��� 270 V 18 ��� 36 V
M22378
-
M223780030000
-
-
Current measurement circuit
Nominal current (In)
DHC-96 mAdc
± 20 mA / 0... 20 mA / 4... 20 mA
DHC-96 Adc
1 A / 5 A
Overload
1.2 In continuous, 10 In Instantaneous (5s)
Consumption
< 0.2 VA
Impedance
DHC-96 mAdc
< 10 Ω
DHC-96 Adc
< 20 mΩ
Installation category
CAT III 300V
Measurement accuracy
Current measurement
0.5%
Relays outputs
Quantity
2
Contact capacity (resistive)
CA:
5A / 250 V~ ,
CC:
5A / 30 V
Max� voltage open contacts
277 V~
Maximum current
5 A ~
Maximum switching power
1385 VA
Electrical life (250 V
~
/ 5A)
1x10
5
Mechanical life
5x10
6
Digital inputs
Quantity
2
Type
Potential free contact
Insulation
2000 V~
Maximum short-circuit current
3.3 mA
40
DHC-96 mAdc, DHC-96 Adc
Instruction Manual
Summary of Contents for DHC-96 Adc
Page 1: ...INSTRUCTION MANUAL M227B01 03 22A DC Ammeter DHC 96 mAdc DHC 96 Adc...
Page 2: ...2 DHC 96 mAdc DHC 96 Adc Instruction Manual...
Page 44: ...10 CE CERTIFICATE 44 DHC 96 mAdc DHC 96 Adc Instruction Manual...
Page 45: ...45 Instruction Manual DHC 96 mAdc DHC 96 Adc...
Page 46: ...46 DHC 96 mAdc DHC 96 Adc Instruction Manual...