6�3�3�- DIGITAL INPUTS
For these variables is implemented the
Function
0x02�
Table 35: Modbus memory map (Table 4)
Parameter
Format
Address
Digital input
bit
0000
The format of the parameter is shown in
Table 36:Format of the variables : Digital inputs�
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
0
0
0
0
0
Digital input 2
1:
closed
0:
open
Digital input 1
1:
closed
0:
open
6�3�4�- REMOTE CONTROL OUTPUT (Relay output)
For these variables is implemented the
Function
0x05:
Table 37:Modbus memory map (Table 4)
Parameter
Format
Address
Value
Remote control, Output relay 1
bit
0000
0000:
open
FF00:
closed
Remote control, Output relay 2
bit
0001
0000:
open
FF00:
closed
Function 0x0F,
multiple relay control:
Table 38: Modbus memory map (Table 5)
Parameter
Format
Address
Remote control
bit
0000
The format of the parameter is shown in
Table 39:Format of the variables: Remote control�
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
0
0
0
0
0
Relay 2
1:
Closed
0:
Open
Relay 1
1:
Closed
0:
Open
37
Instruction Manual
DHC-96 mAdc, DHC-96 Adc
Summary of Contents for DHC-96 Adc
Page 1: ...INSTRUCTION MANUAL M227B01 03 22A DC Ammeter DHC 96 mAdc DHC 96 Adc...
Page 2: ...2 DHC 96 mAdc DHC 96 Adc Instruction Manual...
Page 44: ...10 CE CERTIFICATE 44 DHC 96 mAdc DHC 96 Adc Instruction Manual...
Page 45: ...45 Instruction Manual DHC 96 mAdc DHC 96 Adc...
Page 46: ...46 DHC 96 mAdc DHC 96 Adc Instruction Manual...