31
Instruction Manual
CVM-D41 DC
Table 23: Value of the A variable�
Analog output
parameter
A
V, voltage
PT-1
I, current
CT-1
P, power
PT-1 x CT-1
(1)
(1
)
The 4 most significant digits.
Note:
FS
(End of the analog output)
-
DS
(Start of the analog output) ≥ 500
To validate the data, press the
key.
Use the
and
keys to browse the configuration screens of the menu.
5�3�4�-READING FOR THE END OF THE ANALOG OUTPUT
In this screen, the reading value from which the analog output ends is configured.
FS
1000
V
Use the
, key to modify the value of the flashing digit
When the desired value is shown on the screen, press the
key to skip the digit.
Configuration values
Table 24: Configuration values: Reading for the end of the analog output�
Reading for the end of the analog output
Minimum value
> 0.5 x
A
1.2 x
A
, for the analog output of the voltage measurement,
1.2 x
A
, for the analog output of the current measurement
Maximum value PT-1 x CT-1
, for the analog output of the power measurement.
Note:
The value of the
A
variable varies depending on the
analog output parameter
programmed, see
.
Note:
FS
(End of the analog output)
-
DS
(Start of the analog output) ≥ 500
To validate the data, press the
key.
Use the
and
keys to browse the configuration screens of the menu.
5�3�5�- SAVE CONFIGURATION
To save the configuration of the device, follow the steps indicated in section
�