![Circutor CVM-B100 Instruction Manual Download Page 12](http://html1.mh-extra.com/html/circutor/cvm-b100/cvm-b100_instruction-manual_2608271012.webp)
12
M-CVM-B-DATALOGGER XML Manual
Instruction Manual
Tabla 7 (Continuation) : Parameter description (2�6) (Table 1)
Parameter
Description
fieldARM
Harmonic value register
fieldFO
Waveform value record
fieldEVQ
EVQ event register
Here are the different types of values that can be returned by this request:
Standard value registers (voltages, currents, power, energy, etc.).
<field>
<id> … </id>
<value> … </value>
</field>
Table 8:Parameter description (2�6) ( Table 2)
Parameter
Description
id
Variable identifier (device.variable)
value
Value
Complex value register (PLT, etc.).
<fieldComplex>
<id> … </id>
<value> … </value>
<flags> … </flags>
</fieldComplex>
Table 9:Parameter description (2�6) ( Table 3)
Parameter
Description
id
Variable identifier (device.variable)
value
Value
flags
Additional information from the variable formed by the union of one or more of the
following values:
0x0000
: The PLT is correct
0x0001
: The PLT calculation has been done with fewer samples than expected
0x0002
: The PLT calculation has been done with more samples than expected
0x0004
: The samples used in the PLT calculation do not have an equidistant
separation in the sampling window
0x0008
: Some PST used in the calculation of the PLT contain events in phase 1
0x0010
: Some PST used in the calculation of the PLT contain events in phase 2
0x0020
: Some PST used in the calculation of the PLT contain events in phase 3
0x0040
: Some PST used in the calculation of the PLT are not complete