● When programming the
Zero
and the
Full-scale
value:
Zero
is the value for which you have the start of the analogue output, 0 or 4mA.
The
Full-scale
is the value for which you have the end of the analogue output, 20mA.
Zero Value:
Maximum and Minimum value
:
Full-scale:
Maximum and Minimum value
:
7�4�4�- MODBUS COMMUNICATIONS
The address of the Modbus memory map depends on the position of the expansion module in
the device.
Slot 1 will be the position of the expansion module installed just behind the standard device,
and Slot 2 the next position...
As the maximum number of expansion modules that can be connected to the device is 4, there
will only be 4 slots.
7�4�4�1�- Programming analogue outputs
The following functions are implemented for these variables:
Function 0x04
: reading registers.
Function 0x10
: Writing multiple registers.
Table 131: Modbus memory map: Analogue outputs, expansion modules (Table 1)�
Configuration of analogue outputs
Configuration variable
Valid data window
Default value
Variable code
and
0
Scale
0:
0 to 20 mA
1:
4 to 20 mA
2:
0 to 10 V
0
Zero
0
Full-scale
-
Module no.
0
0
302
CVM-A1000 - CVM-A1500
Instruction Manual