Note:
The 12 registers of each output must be written and read at once (as a group), otherwise
it will respond with an error.
Table 61: Units and maximum and minimum values of the programming variables of the digital outputs�
Variable
Units
Maximum
Minimum
Phase-neutral voltage
(53)
V
10000 * voltage ratio
(50)
0
Phase-phase voltage
(53)
V
Neutral voltage
(53)
V
Current
mA
10000 *current ratio
(51)
0
Neutral current
mA
Frequency
(54)
Hz
70000
40000
Active power
(52)
W
180 000 000
-180 000 000
Apparent power
(52)
VA
0
Total reactive power
(52)
var
-180 000 000
Inductive reactive power
(52)
var
0
Capacitive reactive power
(52)
var
0
Power factor
(53)
-
100
-100
Cos φ
(53)
º
100
-100
Voltage THD %
(55)
%
1000
0
Current THD %
(55)
%
1000
0
Maximum Demand of Current
mA
10000 *current ratio
(51)
0
Maximum Demand of Active Power
W
180 000 000
0
Maximum Demand of Apparent Power
VA
Instantaneous Flicker (Pinst)
(53)
WA
99999
0
K-factor
(53)
-
9999
0
Voltage peak factor
(53)
-
2000
0
Current peak factor
(53)
-
2000
0
% V Unbalance (Kd)
(54)
-
100000
0
% I Unbalance (Kd)
(54)
-
100000
0
% V Asymmetry(Ka)
(54)
-
100000
0
% I Asymmetry(ka)
(54)
-
100000
0
Quality event
-
1
0
Transient
-
1
0
(50)
The voltage ratio is the ratio between the primary and secondary voltage.
(51)
The current ratio is the ratio between the primary and secondary current.
(52)
The three-phase powers accept up to 540 000 000 W.
(53)
Variables with 2 decimals.
(54)
Variables with 3 decimals.
(55)
Variables with 1 decimals.
247
Instruction Manual
CVM-A1000 - CVM-A1500
Summary of Contents for CVM-A1000
Page 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Page 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Page 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Page 366: ...366 CVM A1000 CVM A1500 Instruction Manual...