Figure 299:
Configuration screen of transistor digital outputs (impulse mode).
The parameter selected is indicated in white.
It is possible that the device may measure energy exceeding its configuration.
Make sure the energy pulses correspond to the maximum energy level admitted
by the installation.
To program the transistor digital output, after configuring the
variable code
and the pulse time
(with the
low period
and
high period
parameters), the following formula provides a method for
calculating the number of output pulses according to the generated energy so that the pulses
do not accumulate.
3600 *
PE
/
PT
>
MP → PE
=
MP * TP
/ 3600
Where:
MP
: Maximum power of the installation in W.
PE
: Pulse energy in Wh (
Energy meter factor
)
TP
:
low period
+
high period
, in seconds.
For example:
If the installation can consume 100kW, a suitable configuration could be pulses
of 10W (
Energy meter factor
) with a
high
and
low period
of 50 ms.
The following options appear in the lower area: