6.- TECHNICAL FEATURES
AC Power supply
Rated voltage
100 ... 520 V
~
Frequency
50 ... 60 Hz
Consumption
Computer SMART III FAST 6
Computer SMART III FAST 12
8 ... 14 VA
9... 15 VA
Installation category
CAT III 300 V
Voltage measurement circuit
Rated voltage
(Un)
230 V
P-N
, 400 V
P-P
Voltage measurement margin
20 to 300 V
P-N
, 35 to 520 V
P-P
Frequency measurement margin
45 ... 65 Hz
Input impedance
660 k
Ω
Minimum measurement voltage
(Vstart)
20 V
P-N
, 35 V
P-P
Installation category
CAT III 300 V
Current measurement circuit
Nominal current
(In)
.../5 A or .../1 A
Current measurement margin
1 to 120 % In
Minimum measurement current
(Istart)
50 mA
Installation category
CAT III 300 V
Leakage current measurement circuit
By means of an earth leakage transformer with a
ratio of 500 turns
Nominal current of the secondary
3 mA
Current measurement margin
10 mA to 1.5 A
Minimum measurement current
(Istart)
10 mA
Measurement accuracy (UNE-EN 61557-12)
Voltage measurement
0.5 % ± 1 digit
Current measurement
0.5 % ± 1 digit
Active power measurement
0.5% ± 2 digits
Reactive power measurement
1% ± 2 digits
Active energy measurement
Class 1
Reactive energy measurement
Class 2
Digital outputs
Model
Computer SMART III FAST 6
Computer SMART III FAST 12
Quantity
6
2
6
2
Type
OPTO MOS
NPN
OPTO MOS
NPN
Maximum voltage
24 V
24 V
24 V
24 V
Maximum current
0.15 A
50 mA
0.15 A
50 mA
Relay outputs
Quantity
2 (fan, alarm)
Maximum voltage, open contacts
1 kV
Maximum current
1 A
Maximum switching power
2500 VA
Electrical life
30x10
3
cycles
Mechanical working life
5x10
6
cycles
104
Computer SMART III FAST
Instruction Manual
Summary of Contents for Computer SMART III FAST 12
Page 2: ...2 Computer SMART III FAST Instruction Manual...
Page 108: ...9 CE CERTIFICATE 108 Computer SMART III FAST Instruction Manual...
Page 109: ...109 Instruction Manual Computer SMART III FAST...
Page 110: ...110 Computer SMART III FAST Instruction Manual...
Page 111: ...111 Instruction Manual Computer SMART III FAST...