Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the device switches to the simulation screen,
.
5�23�- COS
φ
LOW ALARM
In this point the lower limit for action of the cos
φ
alarm can be configured. It is activated every time
the value of the cos
φ
drops below the configured value and the current is higher than programmed.
Note:
The alarm must be enabled (
).
Press the
key to enter edit mode. It is identified by the
symbol and the flashing of the
digits to be modified.
In order to avoid possible false activations of said alarms, they have a predefined delay of 15 seconds.
The parameters to be configured are:
The
current value�
The
cos
φ
value
, it is inductive
L
.
The
key increases the digit value or shows the next option.
The
key reduces the digit value or shows the next option.
The
key skips to the previous digit and the
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Current:
Maximum value:
9999 A
Minimum value:
0 A
cos
φ
:
Maximum value:
1.00
Minimum value:
0.50
97
Instruction Manual
Computer SMART III