Figure 12:Circuit breaker�
4�6�2�- CirCAMP-2IP MODEL
The
CirCAMP-2IP
model does not have circuit breakers located inside the unit.
It has two relays (terminals 25... 28 of
Table 4
)
for controlling the external circuit breakers.
The cut-off can be generated:
By an order�
The manager can send a command to open a circuit breaker via any
communications port. These orders are usually used for:
● Cut offs or Reclosures for managing unpaid accounts.
● Commencing or terminating supply service.
The circuit breaker can only be reclosed via another communications command.
Depending on the contracted power
. A different power threshold can be configured
for each circuit breaker, which opens the circuit breaker in the case that the power
demanded by the customer is exceeded.
The circuit breaker is reclosed automatically after 2
n
minutes have passed, with
n
being
the number of attempted retries. Or automatically, via the reclose input of the
CirCAMP-
2IP
.
The reclose input is located in terminals 36 and 37 of the device, see
Table 4
and
Figure 12�
20
CirCAMP-4DP, CirCAMP-2IP
Instruction Manual