Active Periodic Cooling (APC) function behavior at
“cooling for a set ( clS)” mode given in the graph for
below parameters .
APC Parameters
Display
settings
Cooling mode
clF
clS
Cooling start time
cb
on
Cooling cycle
cPr
24 h
Cooling set point C ( set –adjusted data)
cSt
-8.0 C
Cooling set point F ( set –adjusted data)
FSt
-15 F
Waiting time in cooling set point
cth
20 min
Max cooling time
hct
120 min
Humidification*
chu
on
Humidification Time*
cht
10 min.
Max humidity during humidification*
chh
80 RH%
Cooling fan activation**
cFn
on
* only for models equipped with humidifier
**only for models equipped with cooling fan
System repeats APC behavior every cPr time.
In a power outage, cooling cycle time cPr is not
reset, It will continue from last recorded time.
Example:
if there is an 1 hour power cut, the next
cooling time will delay about 1 hour.
Remaining time to next cooling can be checked by
the controller
( see page 9)