Total Solution for Industrial Automation
60
Hybrid Xpanel User’s Manual
4)
PLC is not operating.
Major failure could have occurred during PLC’s operation.
Confirm the error code in [online] – [PLC status] and eliminate the factor. Convert PLC
operation status to Run.
(*) Please refer to the [Help] in CICON to get information about all error codes and
countermeasures.
The following are the error codes that could typically occur in PLC major failure. Take
appropriate measures after confirming product malfunction.
I.
0x0109 Error (Error for PBT Check Sum)
This error may occur when a CICON project is damaged while downloading to PLC
CPU. You can resolve this error by following the steps below.
a)
Download a project and check the operation of PLC.
b)
Convert the power of PLC Off to On and repeat a).
c)
Write the project again and repeat a).
Contact CIMON service center if the error persists.
Summary of Contents for CM-HP07CD-AER
Page 1: ......
Page 80: ...01 11 2019 ...