Installation
2-9
3916 Service Delivery Switch
Hardware Installation and Start-up Manual
009-3226-001 Standard Revision E
Copyright
©
2013-2015 Ciena
®
Corporation
July 2015
Installing Power to a 3916 DC System
The 3916 is offered in only one chassis size with DC power, the 3916 DC
Standard (170-3916-901). This system includes a single integrated DC power
supply. The DC power supply operates at +/- 24 VDC or +/- 48 VDC, drawing
a maximum of 2 Amps.
For installations using 24 V input voltage, the recommended fuse value is a
minimum of 5 Amps. For systems using 48 V input voltage, the recommended
fuse value is a minimum of 2.5 Amps.
The DC power cord should be 14 AWG - 18 AWG wire. You will need to install
fork terminal spade lugs on the power cord to ensure a proper connection with
the terminal block of the power supply.
contains a summary of the
recommended locking fork terminal lugs.
See
“Installing a DC Power Cable” on page 2-34
for a procedure.
Table 2-1
3916 DC Lug Summary
Wire Size
Stud
Maximum Lug Width
Recommended Lug
14 AWG
#6
0.31”
Panduit PV14-6FF-C (16-14 AWG)
14 and 18
AWG
#6
0.31”
Panduit PV14-6LF-C (18-14 AWG)
Panduit PV14-6LFW-C (18-14 AWG)
18 AWG
#6
0.31”
Panduit PV18-6FF-CY (22-16 AWG)
Panduit PV18-6LF-CY (22-18 AWG)
Panduit PV18-6LFW-CY (22-18 AWG)
Note:
Use one of these recommended lugs or a close equivalent. If a ring lug is used, you will need to
remove and reinstall the screw. Take care not to lose the screw during this process.
WARNING
Do not strip more than the recommended amount of wire.
Stripping more than the recommended amount can create a
safety hazard by leaving exposed wire on the terminal block
after installation.
WARNING
A readily accessible disconnect device shall be incorporated
external to the equipment.