![Cichewicz Futura Bio 100 Installation, Operation And Maintenance Instructions Download Page 18](http://html1.mh-extra.com/html/cichewicz/futura-bio-100/futura-bio-100_installation-operation-and-maintenance-instructions_2606839018.webp)
18
fuel feeding time and intervals between fuel feeding operations during start-up and working cycle (see
instruction manual for boiler controller).
6. Fuel feeding times should be so programmed that the previous fuel portion burns completely before the
fuel does not pour through into ash box and the embers do not move backwards to the feeder. It is the
best when combustion takes place on two-thirds of burner’s surface area.
may go out.
8. Also, it is necessary to adjust the volume of combustion air fed to the boiler by adequate setting of the fan
operation (using fan shutter or from controller level). The volume of air should be so adjusted that the
9. Periodically (at least once a week) check the settings of fuel feeder and burner, as well as the combustion
process in the boiler.
Damping
to ash box.
Then empty the ash box from ash and remaining embers and close the boiler door.
occur.
Futura Bio Pellet
Firing up
1. Fill the tank with fuel.
2. Connect the boiler to power supply line (put the cable plug into wall socket).
quantity of starting fuel portion, fuel feeding time and intervals between fuel feeding operations during
start-up and working cycle for minimum and maximum boiler output (see instruction manual for boiler
controller).
6. Fuel feeding times should be so programmed that the previous fuel portion burns completely before the
fuel does not pour through into ash box and the embers do not move backwards to the feeder. It is the
best when combustion takes place on two-thirds of burner’s surface area.
may go out.
8. Also, it is necessary to adjust the volume of combustion air fed to the boiler by adequate setting of the fan
operation (using fan shutter or from controller level). The volume of air should be so adjusted that the
9. Periodically (at least once a week) check the settings of fuel feeder and burner, as well as the combustion
process in the boiler.
After initial adjustment the controller will automatically adjust the metering of fuel and air for the set
boiler output.
Damping
automatically. The burner damps each time the set temperature is reached.
Attention: Combustion of various fuels on grates under the burner may cause burner damage. These grates
are designed for burning the remaining embers from the burner and are not intended for continuous
combustion.
Note:
water and the valve open, so as water remains in tubing.
In case of water depletion in the tank, check the tightness of wax plug located on the feeder. If leaks are
found, remove used wax and pout in a new one.