Control manual

V300

12 - 2016

NA 12.54 D

Summary of Contents for V300

Page 1: ...Control manual V300 12 2016 NA 12 54 D ...

Page 2: ......

Page 3: ...LATION PARAMETERS 7 8 DIAGNOSTICS 9 9 WIRING SCHEMATIC DIAGRAM FOR INDIVIDUAL UNITS 10 10 MEASURING THE TEMPERATURE 11 11 CHARACTERISTICS OF THE SENSORS USED BY THE V300 12 12 MEASURING THE WATER TEMPERATURE 12 13 RADIO FREQUENCY TERMINAL 13 14 MASTER SLAVE FUNCTION 14 15 PI CONTROL 17 16 UNIVERSAL INPUTS 17 17 CONNECTING THE FRAME CONTACT 18 18 CENTRALISED MANAGEMENT WITH V300 19 19 ELECTRICAL CO...

Page 4: ...d and used in accordance with these instructions Important this equipment has been found to comply with the essential requirements of the directives in reference to the following standards Electromagnetic compatibility 2014 30 EU Low voltage directives 2014 35 EU Directive concerning the restriction of the use of hazardous substances in electrical and electronic equipment RoHS 2011 65 EU 1 3 Use T...

Page 5: ... 4 tube Heating 0 1 Cooling 0 1 Labelling AA Note These values are obtained with the CIAT NTC 10k Ω return air temperature sensor at 25 C These values can be viewed on the Eubac certification website http www eubaccert eu General danger If the instructions are not followed there is a risk of equipment damage Electrical danger If the instructions are not followed there is a risk of electrocution an...

Page 6: ...h the unit on or to standby and if applicable to measure the room temperature The connection between the terminal and the controller is a 4 wire connection 2 shielded twisted pairs with the shielding connected to the comfort unit earth see pp 10 16 Regulation on the air The regulation V300 also allows a functioning on the air without gate crack In this case the use of pumps of condensats on device...

Page 7: ...y was pressed It also displays error messages reports windows opened or emergency switch off activation thereby enabling an initial diagnostic 2 Temperature adjustment keys or These enable you to adjust the temperature setpoint and also access the set up and diagnostic values 4 K default setting adjustable by parameter 3 Standby key This enables you to change the operating mode comfort economy fro...

Page 8: ...ection symbol No ventilation indication Off set using the zone timer or sleep button on the terminal depending on configuration Off symbol No ventilation indication Setpoint adjustment Setpoint adjustment depends on the configuration 4 K by default Ventilation 1 2 or 3 LS MS or HS manual selected AUTO ventilation controlled automatically by the controller Indoor environment sensor fault if indoor ...

Page 9: ...ode P04 0 5 P03 2 0 increments of 0 5 19 0 X P03 Cooling comfort setpoint Setpoint for cooling control in comfort mode P02 2 0 P05 0 5 increments of 0 5 26 0 X P04 Economy heating setpoint Heating control setpoint in economy mode P53 0 5 P02 0 5 increments of 0 5 14 0 X P05 Economy cooling setpoint Cooling control setpoint in economy mode P03 0 5 40 increments of 0 5 32 0 X P06 Comfort setpoint se...

Page 10: ...control 1 Frost protection 2 Economy 3 Alarm HEE motor 4 LS air purification 5 MS air purification 6 Off 0 6 3 X P18 Number of fan speeds 0 3 speeds in all modes 1 3 speeds in comfort mode 2 speeds in reduced mode 0 1 0 X P19 Deadband ventilation 0 Ventilation off in all modes 1 Periodic restarts in comfort mode off in economy and frost protection mode 2 Periodic restarts in all modes 3 Permanent ...

Page 11: ...ate 011 Heating and cooling authorised 001 Heating authorisation 010 Cooling authorisation d4 Electrical authorisation state 0 Electric heating bypassed 1 Electric heating authorised d5 Mode active 0 Off 1 Frost protection 2 Economy 3 Comfort d6 Digital input state 000 DI2 closed DI1 closed 001 DI2 closed DI1 open 010 DI2 open DI1 closed 011 DI2 open DI1 open d7 Alarm 000 No alarm 001 Sensor fault...

Page 12: ...ARC Equipment to be provided by the customer CIAT assembly optional Customer connection Shielded twisted pair Customer connection if component supplied separately Multi conductor cable Earth terminal Earth Controller Terminal connection shielded twisted cable see p20 Shielding to be connected to terminal 23 on the controller and terminal end Certain problems may be resolved by checking some fundam...

Page 13: ...er sensor in case of a reversible 2 tube coil is correctly electrically connected and that the sensing element is in contact with the water inlet pipe The controller is correctly set up refer to the Installation parameters procedure If operating with an electric heater check that the T C limiter is activated No refrigeration Check that The cooling setpoint temperature is less than the measured and...

Page 14: ... the pipe s thermal insulation Position and use of the changeover sensor Sensor Valve motor 3 way valve with built in bypass often called a 4 way valve Insulation Water inlet pipe Clamp Sensor adapter Sensor 20 cm min 150 cm 150 cm Changeover operating algorithm If the changeover sensor measures a water temperature greater than 7 C P48 adjustable at room temperature the water is deemed to be hot I...

Page 15: ...placed with the wrong type Dispose of used batteries in accordance with the instructions When replacing batteries make sure the product is correctly and completely refitted IMPORTANT for Switzerland Annex 4 10 to the norm SR 814 013 is applicable to batteries Configuring the terminal with its receiver Radio receiver Indicator 1 blue Flashes receiver not paired rapid flashing receiver not paired On...

Page 16: ...unicates the following information to the slaves Setpoints Air temperature Water temperature Current mode Manual ventilation speed State of inputs D1 and D2 It is possible via P11 to set the slave units on the return air sensor e g open plan offices A slave must not have a room unit The operation resulting from the combination of the Off Frost protection Economy Comfort Window open states between ...

Page 17: ...r the orders from the Master and its room terminal If the Input is configured to one of the 4 operating modes If triggered on the master The entire Master Slave loop switches to the mode defined by the input configuration Only a lower mode may be set using the wall mounted terminal depending on the sleep button configuration For window switches Frost protection mode They must all be connected in s...

Page 18: ...V300 22 23 5V A B 31 27 28 29 30 D1 24 25 26 A B D2 06 07 08 EH 10A A D N 1 2 Q D N 1 2 Q D N 1 2 Q Max length of bus cable between 2 slaves 30m Max length of bus cable between the master and the 1st slave 30m including cable length for room terminal MASTER SLAVE 1 SLAVE N POWER IN 230 V POWER IN 230 V POWER IN 230 V POWER SUPPLY CONTROLLER FAN Blue Brown Blue Brown Blue Brown MAX 15 SLAVES MASTER...

Page 19: ...d ventilation P19 3 or have constant ventilation in the summer and for it to cut out in the winter P19 5 i e ventilation on every 30 mins for 1 minute P19 2 If control is applied using the return sensor it is strongly recommended to have continuous low speed ventilation The setting of these parameters is derived from a compromise between control precision physiological comfort and energy saving se...

Page 20: ...e connected to the Master unit all contacts in series normally closed default Direction of window switch The cable used has a maximum length of 10 m and minimum section of 0 9 mm It is recommended to use a twisted and shielded cable Note the window switch must be insulated from earth If there is shielding present it must be connected to the comfort unit earth Window switch Regulator Connecting the...

Page 21: ...eating and cooling Economy setpoints To override the time slots per zone or for the entire building The zone controller therefore enables management of the entire building for The locally authorised setpoint shift range Adjustment of the comfort restart time on the local wall mounted terminal Possible central changeover Advance heating restart based on the outdoor temperature depending on options ...

Page 22: ... shielding continuity and shielding connected to the Master comfort unit earth Pair 1 A and B polarity to be observed Pair 2 if existing Shielding continuity between the Master and Slave controllers Max capacity between cables 150 Cc m Filotex FMA 2P type cable Belden ref 9842 9842NH 24AWG or equivalent 2 shielded twisted pairs Window contact input Wiring 2 x 1 mm2 shielded twisted with shielding ...

Page 23: ...oduct manufactured in the week REF 7335301 FAB 1625 0001 LOG V2 0 Made in France 2016 Screws Screws Screws Male faston terminals 2 8 x 0 8 Quick release connector Controller wiring diagram Colour RAL 9010 Wired wall mounted and radio frequency version 20 TERMINAL DIMENSIONS ...

Page 24: ... or COOLING depends on the water temperature If the water is hot the unit can heat If the water is cold the unit can heat and cool 21 USING THE USER TERMINALS Technical caracteristics Power supply Standards directives Supply voltage 220 240Vac 50 60 Hz Index of Protection IP 20 in accordance with EN 6059 Max consumption 2 5W Insulation class Class II in accordance with EN 60335 1 Frost protection ...

Page 25: ......

Page 26: ...dustrielle d Applications Thermiques Corporation with a capital of 26 728 480 R C S Bourg en Bresse B 545 620 114 CIAT Service www ciat fr This document is not legally binding As part of its continuous drive to improve its equipment CIAT reserves the right to make any technical modifications without prior notice With Ecofolio all papers can be recycled ...