background image

01 - 2009

NA 08.144 A

Aquaciat Fr

ee cooling

Installation

Operation

Commissioning

Maintenance

Summary of Contents for LDC 1000V

Page 1: ...01 2009 NA 08 144 A Aquaciat Free cooling Installation Operation Commissioning Maintenance...

Page 2: ...Think safety 2 Warranty 2 Storage 2 Installation 2 Hydraulic diagram 6 Hydraulic pumps 6 Performance of chillers and free cooling modules 7 Chillers technical data 8 Free cooling module technical dat...

Page 3: ...sioning For long term storage over 3 months fill the exchanger with an inert gas and seal the pipes hermetically to avoid any condensation and subsequent oxidation see also the section on Maintenance...

Page 4: ...impacts or scratches which may affect the unit s ability to operate correctly perforation of the elbows damage to the finned surface twisting of piping initial corrosion 2 units A 2 m 3 or more units...

Page 5: ...zes LDC LDH Empty In operation Empty In operation 702V 3103 3234 3253 3884 800V 3143 3274 3293 3924 900V 3198 3329 3348 3979 1000V 3238 3369 3388 4019 1100V 3368 3499 3488 4119 1200V 5763 6123 5888 67...

Page 6: ...f valves on the inlet and outlet pipes The unit must be fitted with an emergency stop device located very nearby this device must be visible and accessible and must allow the electrical supply to the...

Page 7: ...oduce foreign bodies into the circuit Hydraulic diagram Hydraulic pumps C and H versions 1 2 air bleed valve 1 2 water drainage valve Flow rate controller Drain valve automatic Size 1200 1800 Manual b...

Page 8: ...0 321 0 364 0 421 0 471 0 Chiller s absorbed power kW 60 4 70 6 81 7 90 9 102 0 110 9 129 6 146 0 164 4 Chiller s EER efficiency 3 00 2 83 2 95 2 84 2 72 2 89 2 81 2 88 2 87 Lw Lp LN version 3 dB A 84...

Page 9: ...rmer fitted Evaporator Brazed plate heat exchangers Water capacity l 15 8 15 8 18 20 4 20 4 26 33 5 37 40 5 Chilled water outlet temp min max C 12 18 Minimum water flow rate m3 h 22 1 24 4 29 3 31 6 3...

Page 10: ...6 34 38 43 50 56 Maximum water flow m3 h 63 2 69 5 77 77 77 106 110 110 110 Water connection dia DN 100 FLANGE DN 125 FLANGE Max pressure water end bar 4 bar Storage temperature C 50 AQUACIAT FREE COO...

Page 11: ...on top of the unit Periodically check the condition of the anti corrosion protective coating and touch it up if necessary The category DESP as specified by directive 97 23 EC is indicated on the spec...

Page 12: ...the unit from its power sources Drain the unit respecting the environmental standards Use the original lifting rings If the signs relating to lifting have been removed anchoring points slinging instr...

Page 13: ...odification CIAT Service Tel 33 0 4 79 42 42 90 Fax 33 0 4 79 42 42 13 Si ge social Avenue Jean Falconnier B P 14 01350 Culoz France Tel 33 0 4 79 42 42 42 Fax 33 0 4 79 42 42 10 info ciat fr www ciat...