19 - TROUBLESHOOTING

Important: when carrying out repairs, always use original parts, paying particular attention to their installation, as all parts 

must remain in their original positions.

Symptom

Cause

Solution

Condensation temperature too low

a) Insufficient gas

b) Obstacle in the expansion component

a) Look for leaks and top up the charge

b) Check the expansion valve

Condensation pressure too high compared to the 

discharge air, high pressure alarm

a) Insufficient air flow

b) Air intake temperature too high

c) Condenser fouled (no exchange)

d) Excessive refrigerant charge (condenser flooded)

e) The condenser fan is faulty

f) Air in the refrigerating circuit

a) Check the condenser fan

b) Check the condensation regulation setting

c) Clean it

d) Bleed

e) Repair

f) Bleed

The compressor does not start

a) Power supply fault

b) The contacts of a control components are open

c) Contactor coil blown

d) Internal electronic thermistor thermostat open

a) Check the differential and fuses

b) Check the safety chain

c) Replace it

d) Wait for the restart and check the input current

The compressor does not start, the motor makes an 

intermittent noise

a) Network voltage very low

b) Power supply cable disconnected

a) Check the line voltage and locate the voltage drop

b) Check the connections

The compressor stops and starts repeatedly

a) External control contact cycling too rapidly

a) Insufficient gas.

c) Evaporator fouled

d) The evaporator fan or accelerator pump is not working.

e) Expansion device damaged or blocked by impurities

f) Dehumidifier filter blocked.

a) Adjust the control (increase the control differential)

b) Look for the leak and recharge the equipment

c) Clean it

d) Repair or replace it

e) Replace it

f) Replace it

The compressor is noisy

a) Mounting loose

b) Insufficient oil

c) Noise inside the compressor

a) Retighten

b) Add oil to the recommended level

c) Replace it

Noisy operation

a) unit installed without anti-vibration protection

a) Place the base on anti-vibration mountings

Evaporation pressure too low.

a) Insufficient flow rate in the evaporator 

b) Evaporator frozen (for air evaporators)

c) Expansion valve blocked

a) Insufficient gas

e) Condensation temperature very low

f) Evaporator fan or accelerator pump faulty

a) Check the flow rates

b) Check the defrosting

c) Remove and clean the expansion valve

d) Look for the leak and top up the charge

e) Air temperature in the condenser very low (air flow rate 

very high), adjust the flow rate using the dial on the CL 

control board

f) Repair it

CONDENCIAT

®

 CL2 

EN-14 

 

Summary of Contents for CONDENCIAT CL2

Page 1: ...Instruction manual 11 2021 EN7579254 01 CONDENCIAT CL2 11 2021 EN7579254 01 ...

Page 2: ......

Page 3: ...HANDLING 5 8 OPERATING LIMITS 5 9 TECHNICAL SPECIFICATIONS 5 10 ELECTRICAL SPECIFICATIONS 5 11 DIMENSIONS 6 12 INSTALLATION 8 13 ELECTRICAL CONNECTIONS 9 14 SETTING THE CONTROL AND SAFETY DEVICES 9 15 REFRIGERANT CONNECTIONS 10 16 PRESSURE AND CHARGE TEST 11 17 COMMISSIONING 12 18 SERVICING AND MAINTENANCE 13 19 TROUBLESHOOTING 14 20 DECLARATION OF CONFORMITY 15 21 WARRANTY 15 CONTENTS ...

Page 4: ...rant Presence of voltage Site of installation Temperatures up to 150 C Only experienced and qualified persons may work on this equipment The recommendations and instructions given in the maintenance brochures and the special instructions on the labels must be followed Always comply with applicable standards and regulations IMPORTANT before carrying out any work on the unit make sure it is powered ...

Page 5: ... tubes aluminium fins Fan Type Propeller Quantity 1 2 Nominal flow rate m3 h 2350 2770 4700 5540 5000 Speed RPM 700 904 700 904 Weight kg 69 69 101 112 118 Refrigerant connections Liquid line inch 3 8 1 2 Gas line inch 5 8 3 4 7 8 10 ELECTRICAL SPECIFICATIONS CONDENCIAT CL2 28 35 50 65 75 Compressor Voltage 400 V 3 Ph 50 Hz Maximum current A 6 9 8 0 10 3 15 0 15 0 Fans Maximum current A 0 46 0 97 ...

Page 6: ...ance 350 350 100 100 170 602 1035 263 410 27 705 377 5 45 450 5 B C 2 holes Ø8 2 100 263 602 170 A 20 20 410 for fixing the mounts to the floor Detail A Position of holes for fixing the anti vibration mounts to the floor Four fixing points HM8 x 55 screw 90 B C 137 5 Outdoor air flow direction B LIQUID line C INTAKE GAS line CONDENCIAT CL2 EN 6 ...

Page 7: ...0 5 B C 27 1305 600 377 5 45 2 holes Detail A Position of holes for fixing the anti vibration mounts to the floor 4 fixing points HM8 x 55 screws for fixing the mounts to the floor Ø8 2 100 A 20 20 410 263 602 170 90 B C 137 5 Outdoor air flow direction B LIQUID line C INTAKE GAS line Anti vibration mounts are fitted to the heat pump using 4 x HM8 screws 55 mm in length EN 7 CONDENCIAT CL2 ...

Page 8: ...n Min Min Installation on soft ground 200 mm 200 mm Concrete foundations Installation on concrete ground 200 mm 200 mm Concrete foundation Nothing should obstruct the free flow of air over the air cooled exchanger Adhere to the minimum distances shown above Protect from prevailing winds CONDENCIAT CL2 EN 8 ...

Page 9: ...eristics the distance of the unit from the main supply point the upstream protection and the neutral operating conditions IMPORTANT Connect the unit to earth before making any other electrical connections A main cut off switch must be installed on the unit Cable routing Detail of electrics box supply External control input this potential free dry contact positioned between terminals 1 and 2 is use...

Page 10: ... and deoxidised suitable for an operating pressure of at least 4200 kPa and minimum burst pressure of 20 700 kPa Domestic water type copper pipes must never be used Smooth the ends of the pipes by inclining them downwards Make sure there is no contamination inside the pipes Remove the flare nuts from the unit and place them on the pipe Flare the ends of the pipes Characteristics of a properly flar...

Page 11: ...ressure pressostat Before starting up the compressor check that the operations below have been carried out Electrical connection check that all the connections are correctly tightened and that the voltage is stable and in accordance with the data on the manufacturer s data plate Connecting the refrigeration lines Pressure test Evacuation To charge with R410A fluid if it is not possible to fill the...

Page 12: ...evented Date Time CONDENCIAT CL2 operating readings System start up date Serial No Installer Site of installation Model 28o 35o 50o 65o 75o Compressor Suction pressure bar Intake temperature C Condensation pressure bar Condensing temperature C Air cooled condenser Gas inlet temperature C Liquid outlet temperature C Air inlet temperature C Air outlet temperature C Nominal voltage V Voltage at termi...

Page 13: ...ment 1 No impact on the OZONE layer ODP Ozone Depletion Potential rating 0 2 Impact on the greenhouse effect GWP Global Warming Potential 2088 Users must have units containing over 3 kg of refrigerant periodically checked for leaks by qualified personnel 2 kg in France decree and order of 7 May 2007 Regardless of the refrigerant charge in your system CIAT requires that this check be carried out in...

Page 14: ... very low b Power supply cable disconnected a Check the line voltage and locate the voltage drop b Check the connections The compressor stops and starts repeatedly a External control contact cycling too rapidly a Insufficient gas c Evaporator fouled d The evaporator fan or accelerator pump is not working e Expansion device damaged or blocked by impurities f Dehumidifier filter blocked a Adjust the...

Page 15: ... Conformity This unit complies with the requirements of Electrical Equipement Safety Regulations 2016 Electromagnetic Compatibility Regulations 2016 The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012 UK Importer Toshiba Carrier UK Ltd Porsham Close Roborough Plymouth PL6 7DB 21 WARRANTY See our general terms and conditions of sale EN ...

Page 16: ...Manufacturer Carrier S C S Rte de Thil 01120 Montluel France Printed in the European Union Manufacturer reserves the right to change any product specifications without notice ...

Reviews: