EN - 37
AQUACIAT
POWER
7 - CONNECT TOUCH CONTROL: MENU STRUCTURE
Heat Reclaim Config Menu – HR_CFG
Name
Status
Default
Unit
Displayed text*
Description
hrVarPmp
no/yes
no
-
HR variable speed pump ?
Heat Reclaim variable-speed pump selection:
no = 3-way valve is used
yes = variable speed pump is used
hr_flui
water/brine
water
-
HR condenser fluid
Heat Reclaim condenser fluid type:
0 = water, 1 = brine
hr_eco
off/on
off
-
HR eco mode ?
Heat Reclaim "Eco" mode:
on = fans disabled in Heat Reclaim (Heat Reclaim efficiency priority)
off = fans enabled in Heat Reclaim (chiller efficiency priority)
rev_3WV
no/yes
no
-
HR reverse 3WV cmd ?
Heat Reclaim 3-way valve reversed command:
NO : 0V = close
no = 0V, 3-way valve fully closed
(water flow depends on "Min flow 3wv position" set in the HR_CFG table)
YES : 0V = open
yes = 0V, 3-way valve fully opened
(there is water flow in the condenser and in the customer loop)
HRewtctl
no/yes
yes
-
HR Control on EWT ?
Heat Reclaim control:
no = HR control on water leaving the 3-way valve
(if the sensor is located after the 3-way valve)
yes = HR control on water entering the 3-way valve
(if the sensor is located before the 3-way valve)
kp_HR3wv
-20 to 20
2
-
PID gain prop 3w valve
3-way valve / pump PID proportional gain
ki_HR3wv
-5 to 5
0.2
-
PID gain int 3w valve
3-way valve / pump PID integral gain
kd_HR3wv
-20 to 20
0.4
-
PID gain deri 3w valve
3-way valve / pump PID derivative gain
kp_HRFan
-20 to 20
5
-
PID gain prop fan
Fan PID proportional gain
ki_HRFan
-5 to 5
0.5
-
PID gain int fan
Fan PID integral gain
kd_HRFan
-20 to 20
0
-
PID gain deri fan
Fan PID derivative gain
minHRpmp
15 to 60
30
%
HR VarPump min pos
Minimum variable-speed pump speed in Heat Reclaim
maxHR3wv
70 to 100
100
%
3WayValve/VarPmp max pos
Maximum 3-way valve position (or variable-speed pump speed) in Heat
Reclaim mode
flowTmr
10 to 120
20
sec
HR delay flow switch
Heat Reclaim flow switch delay timer (see alert 10052)
minFloEn
no/yes
no
-
Min flow 3wv enable
3-way valve minimum flow setting:
no = Anti-freeze protection disabled
yes = Anti-freeze protection enabled. When Heat Reclaim is not active
and the outside air temperature is low, the 3-way valve will be opened to
its pre-configured position ("Min flow 3wv position").
minFlow
10 to 100
15
%
Min flow 3wv position
Minimum 3-way valve position used to ensure minimum fluid flow and
prevent it from freezing
min_wt
-10.0 to 1.1
14.0 to 34.0
1.1
34.0
°C
°F
HR Min water temp
Minimum water temperature in Heat Reclaim mode: If the temperature
drops below this setting, an alert will be raised (10128). HR condenser
heater will be energized (if present), HR mode will be off and the pump will
be turned on.
* Depends on the selected language (French by default).