AQUACIAT

POWER

7 - CONNECT TOUCH CONTROL: MENU STRUCTURE

 Heat Reclaim Config Menu – HR_CFG

Name

Status

Default

Unit

Displayed text*

Description

hrVarPmp

no/yes

no

-

HR variable speed pump ?

Heat Reclaim variable-speed pump selection:

no = 3-way valve is used

yes = variable speed pump is used

hr_flui

water/brine

water

-

HR condenser fluid

Heat Reclaim condenser fluid type:

0 = water, 1 = brine

hr_eco

off/on

off

-

HR eco mode ?

Heat Reclaim "Eco" mode:

on = fans disabled in Heat Reclaim (Heat Reclaim efficiency priority)

off = fans enabled in Heat Reclaim (chiller efficiency priority)

rev_3WV

no/yes

no

-

HR reverse 3WV cmd ?

Heat Reclaim 3-way valve reversed command:

NO : 0V = close

no = 0V, 3-way valve fully closed  

(water flow depends on "Min flow 3wv position" set in the HR_CFG table)

YES : 0V = open

yes = 0V, 3-way valve fully opened  

(there is water flow in the condenser and in the customer loop)

HRewtctl

no/yes

yes

-

HR Control on EWT ?

Heat Reclaim control:
no = HR control on water leaving the 3-way valve  

(if the sensor is located after the 3-way valve)
yes = HR control on water entering the 3-way valve  

(if the sensor is located before the 3-way valve)

kp_HR3wv

-20 to 20

2

-

PID gain prop 3w valve

3-way valve / pump PID proportional gain

ki_HR3wv

-5 to 5

0.2

-

PID gain int 3w valve

3-way valve / pump PID integral gain

kd_HR3wv

-20 to 20

0.4

-

PID gain deri 3w valve

3-way valve / pump PID derivative gain

kp_HRFan

-20 to 20

5

-

PID gain prop fan

Fan PID proportional gain

ki_HRFan

-5 to 5

0.5

-

PID gain int fan

Fan PID integral gain

kd_HRFan

-20 to 20

0

-

PID gain deri fan

Fan PID derivative gain

minHRpmp

15 to 60

30

%

HR VarPump min pos

Minimum variable-speed pump speed in Heat Reclaim

maxHR3wv

70 to 100

100

%

3WayValve/VarPmp max pos

Maximum 3-way valve position (or variable-speed pump speed) in Heat 

Reclaim mode

flowTmr

10 to 120

20

sec

HR delay flow switch

Heat Reclaim flow switch delay timer (see alert 10052)

minFloEn

no/yes

no

-

Min flow 3wv enable

3-way valve minimum flow setting:

no = Anti-freeze protection disabled

yes = Anti-freeze protection enabled. When Heat Reclaim is not active 

and the outside air temperature is low, the 3-way valve will be opened to 

its pre-configured position ("Min flow 3wv position"). 

minFlow

10 to 100

15

%

Min flow 3wv position

Minimum 3-way valve position used to ensure minimum fluid flow and 

prevent it from freezing 

min_wt

-10.0 to 1.1

14.0 to 34.0

1.1

34.0

°C

°F

HR Min water temp

Minimum water temperature in Heat Reclaim mode: If the temperature 

drops below this setting, an alert will be raised (10128). HR condenser 

heater will be energized (if present), HR mode will be off and the pump will 

be turned on.

*  Depends on the selected language (French by default). 

Summary of Contents for AQUACIATPOWER CONNECT TOUCH ILD 602R

Page 1: ...Instruction manual 11 2022 10555 CONNECT TOUCH AQUACIAT POWER I LD 602R 4000R...

Page 2: ...umentation 21 7 CONNECT TOUCH CONTROL MENU STRUCTURE 22 7 1 Main menu 22 7 2 Configuration menu CONFIG 33 7 3 Network Parameters menu 38 7 4 System Menu 40 7 5 Alarm Menu 42 8 STANDARD CONTROL OPERATI...

Page 3: ...ormation provided herein is solely for the purpose of allowing customers to operate and service the equipment and it is not to be reproduced modified or used for any other purpose without the prior co...

Page 4: ...ce engineers should be allowed to install and service the equipment 1 2 Safety precautions Only personnel qualified in accordance with IEC International Electrotechnical Commission recommendations may...

Page 5: ...r to maintain the correct refrigerant pressure in each circuit and monitors safety devices that protect the unit against failure and guarantee its optimal functioning 2 3 Operating modes The control m...

Page 6: ...E mail transmission Occupied Unoccupied mode management Trending Master Slave control Diagnostics Cooling control Free cooling dry cooler mgmt Heating control Boiler heating control Electric heating...

Page 7: ...es on boards All boards continuously check and indicate the proper operation of their electronic circuits A light emitting diode LED lights on each board when it is operating properly The red LED flas...

Page 8: ...used instead of the 3 way valve then this sensor is located on the BPHE condenser inlet Free Cooling water temperature sensor FC option The Free Cooling water temperature sensor is located at the outp...

Page 9: ...AI 10 J9 Allows the user to reset the currently selected setpoint Occupancy override SIOB CIOB EMM DI 01 J1 Used to switch between occupied closed contact and unoccupied mode open contact Demand limi...

Page 10: ...It is active only when the control is in Remote mode Cooling Heating Stp1 Stp2 Auto Stp1 Stp2 Auto Setpoint selection contact open closed open closed 4 7 3 Volt free demand limit selection contact Up...

Page 11: ...Proprietary Protocol This wire is required so that all nodes on the bus share a common ground reference connection If a shield is used then the shield cable should be properly terminated and connected...

Page 12: ...ls such as LEN Proprietary Protocol Modbus RTU It is possible to enable and disable end of line resistors via the System menu see section 7 4 One Ethernet port allows for TCP IP communication BACnet M...

Page 13: ...nfig Main Menu Run Times DC Free Cooling Status Modes Msc Status Hydraulic Free Cooling Heat Reclaim General Parameters Pressures Temperatures Inputs Pump Status Outputs Setpoint Configuration Configu...

Page 14: ...Alarms Current Alarms Alarm History Major Alarm History Software Info Hardware Info CPU Load Network EOL Resistor Date Time Configuration Brightness Language Unit System System Menu Home Main Menu Sys...

Page 15: ...r Alert no action taken on the unit Steady icon Alarm s active on the unit OTHER SCREENS Login screen Parameters screen s Login Confirm advanced access login Save changes Logout Reset the user level a...

Page 16: ...d to start if the period is occupied Network Network The unit is controlled by network commands and allowed to start if the period is occupied Remote Remote The unit is controlled by external commands...

Page 17: ...the time of occupancy 6 When the time schedule is set the selected period will be presented in the form of the green band on the timeline 7 Press the Save button to save your changes or the Cancel bu...

Page 18: ...utton to exit the screen without making modifications NOTE You may also leave the screen by pressing the Back button Security access settings User level security ensures that only authorised users are...

Page 19: ...y unit parameters The Configuration menu gives access to a number of user modifiable parameters such as pump configuration schedule menu etc The Configuration menu is password protected To access the...

Page 20: ...the Save button in the lower left part of the screen IMPORTANT Please make sure that dates are not out of range not existing dates otherwise an error message may be displayed Press or to navigate acro...

Page 21: ...t parameters or unit configuration can be performed via the web browser interface Make sure that your network is protected from malicious attacks and any other security threats Do not provide open acc...

Page 22: ...at Reclaim Heat Reclaim RECLAIM Hydraulic Free Cooling Hydraulic Free Cooling HYD_FC Trendings Trendings TRENDING Setpoint Configuration Setpoints configuration SETPOINT Configuration Menu Configurati...

Page 23: ...e unit is in Network mode the minimum value will be used compared to the status of the external limit switch contact and the demand limit switch setpoint LAG_LIM 0 to 100 0 Lag Capacity Limit Value La...

Page 24: ...mote Setpoint Switch Remote setpoint selection switch LIM_SW1 open close open Limit Switch 1 Demand limit switch 1 LIM_SW2 open close open Limit Switch 2 Demand limit switch 2 Energy Management Module...

Page 25: ...EMEA CP_B1 off on off Compressor B1 Compressor B1 command CP_B2 off on off Compressor B2 Compressor B2 command CP_B3 off on off Compressor B3 Compressor B3 command CP_B4 off on off Compressor B4 Compr...

Page 26: ...ta pressure setpoint delta_p kPa PSI Current Water Delta P Current water delta pressure MxDeltaP kPa PSI Cur Max Water Delta P Maximum current water delta pressure VPMP_CMD 0 to 100 0 Variable Speed P...

Page 27: ...uction circuit A m_lowscb no yes no Low Suction Circuit B Low suction circuit B m_hidgta no yes no High DGT Circuit A High DGT circuit A m_hidgtb no yes no High DGT Circuit B High DGT circuit B m_hipr...

Page 28: ...rs Depends on the selected language French by default Msc Status Menu MSC_STAT Name Status Default Unit Displayed text Description m_ecopmp no yes no Eco Pump Mode Active Eco pump mode status When thi...

Page 29: ...ing override fcCapA FC Capacity A Free Cooling capacity circuit A modeCirA 0 to 3 0 Mode of Circuit A Free Cooling mode circuit A 0 Mechanical Cooling MC only 1 Mixed Cooling MC and FC at the same tim...

Page 30: ...re Depends on the selected language French by default Quick Test 1 Menu QCK_TST1 Name Status Unit Displayed text Description Unit must be in Loff To enable the Quick Test functionality the unit must b...

Page 31: ...aim 3Way Valve cmd 3 way valve command QHR_HTR off on Reclaim BPHE Heater Heat Reclaim BPHE heater HYDRAULIC FREE COOLING Hydraulic Free Cooling Q_FC_EV close open FC Evaporator Valve Free Cooling eva...

Page 32: ...egrated COP Integrated COP reset_en no yes Reset of Energy Counter Parameter set to yes allows to reset the energies displayed in this table reset_da Last Reset Date Last Reset Date reset_ti Last Rese...

Page 33: ...on USERCONF Schedule Menu Schedule menu SCHEDULE Holiday Menu Holiday menu HOLIDAY Date Time Configuration Date time configuration DATETIME Network Parameters Network parameters see section 7 3 NETWOR...

Page 34: ...Unit Displayed text Description pump_seq 0 to 4 1 Pumps Sequence Pumps sequence 0 No Pump 0 No pump 1 One Pump Only 1 One pump only units with one pump 2 Two Pumps Auto 2 Two pumps automatic control 3...

Page 35: ...eset value oat_hrfu 10 to 51 7 14 to 125 10 0 14 0 C F OAT Full Reset Value OAT max reset value dt_hr_no 0 to 13 9 0 to 25 0 0 C F Delta T No Reset Value Delta T no reset value dt_hr_fu 0 to 13 9 0 to...

Page 36: ...Time UTC Location Time zone YYYY MM DD HH MM SS Date Time Current date and time must be set manually no yes Today is a Holiday Information about holidays read only Please note that holidays are set i...

Page 37: ...ID gain int 3w valve 3 way valve pump PID integral gain kd_HR3wv 20 to 20 0 4 PID gain deri 3w valve 3 way valve pump PID derivative gain kp_HRFan 20 to 20 5 PID gain prop fan Fan PID proportional gai...

Page 38: ...P2 0 to 255 0 SMTP IP Addr Part 2 SMTP IP address part 2 smtpP3 0 to 255 0 SMTP IP Addr Part 3 SMTP IP address part 3 smtpP4 0 to 255 0 SMTP IP Addr Part 4 SMTP IP address part 4 accP1 Account Email P...

Page 39: ...mode 1 IR HR in 32 bit mode 1 IR HR in 32 bit mode conifnam 0 to 1 0 IP port interface name IP port interface name 0 J5 J15 0 J5 J15 1 J16 1 J16 timeout 60 to 600 120 sec Com timeout s Com timeout s i...

Page 40: ...of Line Res J7 End of line resistor J7 disable enable disable End of Line Resistor J8 End of line resistor J8 disable enable disable End of Line Resistor J10 End of line resistor J10 Modbus Depends on...

Page 41: ...tch Chinese Italian Portuguese and Custom1 Custom language The control system allows users to add new languages to the control To learn more about language customization please contact your local Serv...

Page 42: ...m 2 index Alarm code see section 9 3 alarm_3 Current Alarm 3 index Alarm code see section 9 3 alarm_4 Current Alarm 4 index Alarm code see section 9 3 alarm_5 Current Alarm 5 index Alarm code see sect...

Page 43: ...topped The pump is running with no mechanical cooling or heating unless configured otherwise The pump may be stopped depending on pumps configuration PUMPCONF Pump Configuration Heating Cooling Standb...

Page 44: ...ing AQUACIATPOWER LD chillers may be fitted with a boiler that allows the unit to run in heating mode if required The boiler is active only when the unit is in Heating mode AQUACIATPOWER ILD heat pump...

Page 45: ...ump protections To mitigate the risk of freezing the water exchanger when the outside air temperature is low the CONNECT TOUCH control provides a means to automatically start the pump each day at 14 0...

Page 46: ...ing auto enable closed unoccupied Cooling setpoint 2 heating sp 1 Heating setpoint 1 heating sp 2 Heating setpoint 2 heating auto occupied Heating setpoint 1 heating auto unoccupied Heating setpoint 2...

Page 47: ...he unit s maximum allowable capacity How to understand capacity limitation Capacity limitation is used to determine the maximum unit s capacity Capacity limitation is expressed in percentage where a l...

Page 48: ...the lead circuit The selected circuit takes priority over another circuit Automatic lead lag circuit determination The control system determines the lead circuit to equalise the operating time of eac...

Page 49: ...ed when the outside air temperature OAT Free Cooling is above the water loop temperature and the service configured threshold parameter However if it turns out that the cooling power of the dry cooler...

Page 50: ...algorithm will ensure minimum water flow on heat exchangers and prevent water boiling It is therefore necessary to permanently guarantee the use or evacuation of the heat transferred to the hydraulic...

Page 51: ...ree defrost is most efficient when current heating demand is below the heating capacity delivered by the unit and the outside air temperature is above 1 C IMPORTANT In the case of a large amount of fr...

Page 52: ...thin 7 days since the first compressor start the alarm will be reset automatically and software options will be blocked The Replacement mode ends when the Software Activation Key is installed or the p...

Page 53: ...nterface in the Reset Alarms menu The Reset alarms menu displays up to 5 alarm codes which are currently active on the unit Alarms can be reset without stopping the machine Only logged in users can re...

Page 54: ...tor reading returns to normal Dry cooler free cooling is disabled Defective thermistor 17 15047 DC Free Cooling Leaving Water Thermistor Failure As above No action alert As above 18 15048 DC Free Cool...

Page 55: ...ual Circuit B shuts down As above 45 10011 Circuit A Low Superheat Manual Circuit A shuts down As above 46 10012 Circuit B Low Superheat Manual Circuit B shuts down As above 47 10014 Customer Interloc...

Page 56: ...lve Failure Automatic No action alert Valve stuck or connection failure 75 10222 FC Evaporator Valve Failure Automatic No action alert Valve stuck or connection failure 76 11201 Water Loop Pressure To...

Page 57: ...atic in the case of cooler flow switch failure high pressure trip or cooler freeze alarm or Manual power cycle required Unit shuts down but the evaporator pump continues to operate Welded contactor of...

Page 58: ...ct CIAT service representative to activate options Automatic if Software Activation Key is installed Automatic if Software Activation Key is not provided within 7 days since the first compressor start...

Page 59: ...inverter OL1 As above 14 Over LOAD in motor OL2 As above 16 Overheat trip OH As above 17 Emergency stop E As above 18 EEPROM fault 1 writing operation EEP1 As above 19 EEPROM fault 2 reading operation...

Page 60: ...que As above 10 Reserved As above 11 Cumulative operation hours reached As above 12 Reserved As above 13 Reserved As above 14 Main circuit undervoltage alarm the same as MS relay status As above 15 At...

Page 61: ...age can occur to your equipment Your local Service Agency provides a wide range of service contracts which embrace the assistance of highly qualified HVAC engineering professionals ready to help if ne...

Page 62: ...AQUACIATPOWER EN 62...

Page 63: ...EN 63 AQUACIATPOWER...

Page 64: ...Manufacturer Carrier SCS Montluel France Printed in the European Union Manufacturer reserves the right to change any product specifications without notice...

Reviews: