7 - ELECTRICAL CONNECTION

Please refer to the certified dimensional drawings, supplied with 

the unit (also available on the internet).

7.1 - Power supply

The power supply must conform to the specification on the unit 

nameplate. The supply voltage must be within the range specified 

in the electrical data table. For connections refer to the wiring 

diagrams and the certified dimensional drawings.

Operation of the unit with an improper supply 

voltage or excessive phase imbalance constitutes 

abuse which will invalidate the CIAT warranty. If the 

phase imbalance exceeds 2% for voltage, or 10% 

for current, contact your local electricity supply at 

once and ensure that the heat pump is not switched 

on until corrective measures have been taken.

7.2 - Voltage phase imbalance (%)

100 x max. deviation from average voltage 

Average voltage

Example:

On a 400 V - 3 ph - 50 Hz supply, the individual phase voltages 

were measured to be:
AB = 406 V; BC = 399 V; AC = 394 V
Average voltage  = (406 + 399 + 394)/3 = 1199/3
 

 

= 399.7 say 400 V

Calculate the maximum deviation from the 400 V average:
(AB) = 406 - 400 = 6
(BC) = 400 - 399 = 1
(CA) = 400 - 394 = 6

The maximum deviation from the average is 6 V. The greatest 

percentage deviation is: 100 x 6/400 = 1.5%
This is less than the permissible 2% and is therefore acceptable.

7.3 - Recommended wire sections

Wire sizing is the responsibility of the installer, and depends on 

the characteristics and regulations applicable to each installation 

site. 

The following is only to be used as a guideline, and 

does not make CIAT in any way liable.

 After wire sizing has 

been  completed,  using  the  certified  dimensional  drawing,  the 

installer must ensure easy connection and define any 

modifications necessary on site.
The  connections  provided  as  standard  for  the  field-supplied 

power entry cables to the general disconnect/isolator switch are 

designed for the number and type of wires, listed in the table 

below.
The calculations are based on the maximum machine current 

(see electrical data tables). Standard installation practises for 

units installed outside have been applied in accordance with IEC 

60364, table 52C:

 

-

No. 17: suspended aerial lines,

 

-

No. 61: buried conduit with a derating coefficient of 20.

The calculation is based on PVC or XLPE insulated cables with 

copper core. A maximum ambient temperature of 40°C has been 

taken into consideration for TD units. The given wire length limits 

the voltage drop to < 5%.

Before connection of  the main power cables (L1 

- L2 - L3) on the terminal block, it is imperative to 

check the correct order of the 3 phases before 

proceeding to the connection on the main 

disconnect/isolator switch.

7.3.1 - Power cable entry

The power cables can enter the TD control box from below or 

from the side of the unit, at the bottom of the angle iron. Pre-

punched holes facilitate the entry. Refer to the certified 

dimensional drawing for the unit. An opening below the control 

box allows introduction of the cables.

7.4 - Field control wiring

Field connection of interface circuits may lead to 

safety  risks:  any  control  box  modification  must 

maintain equipment conformity with local 

regulations. Precautions must be taken to prevent 

accidental electrical contact between circuits 

supplied by different sources:

 

-

The routing selection and/or conductor insulation 

characteristics must ensure dual electric 

insulation.

 

-

In case of accidental disconnection, conductor 

fixing between different conductors and/or in the 

control box prevents any contact between the 

conductor ends and an active energised part.

Refer to the Aquaciat Caléo™ TD Connect Touch Control IOM 

and the certified wiring diagram supplied with the unit for the field 

control wiring of the following features:

 

-

Condenser pump interlock (mandatory)

 

-

Remote on/off switch

 

-

Demand limit external switch

 

-

Remote dual setpoint switch

 

-

Alarm, alert and operation report

7.5 - Power supply

After the unit has been commissioned, the power supply must 

only be disconnected for quick maintenance operations (one day 

maximum). For longer maintenance operations or when the unit 

is taken out of service and stored the power supply must be 

maintained to ensure supply to the heaters (unit frost protection).

Motor

 

 EN-21  AQUACIAT

CALÉO™

 TD

Summary of Contents for AQUACIAT CALEO TD 100

Page 1: ...AQUACIAT CAL O High temperature heat pumps 03 2022 10198 Instruction manual...

Page 2: ...6 APPLICATION DATA 19 6 1 Unit operating range 19 6 2 Plate heat exchanger water flow 19 6 3 Minimum water flow rate 19 6 4 Maximum plate heat exchanger water flow rate 19 6 5 Water loop volume 20 6...

Page 3: ...S WITH FANS WITH AVAILABLE PRESSURE FOR INDOOR INSTALLATION XTRAFAN 34 13 1 Fan discharge connection 34 13 2 Applicable rules for units incorporated into an air duct system 34 13 3 Electrical data for...

Page 4: ...uits are intact especially that no components or pipes have shifted or been damaged e g following a shock If in doubt carry out a leak tightness check If damage is detected upon receipt immediately fi...

Page 5: ...he units are intended to be stored and operate in an environment where the ambient temperature must not be less than the lowest allowable temperature indicated on the nameplate Do not introduce signif...

Page 6: ...Protection device checks If no national regulations exist check the protection devices on site in accordance with standard EN378 once a year for the high pressure switches every five years for extern...

Page 7: ...he certified dimensional drawings for the units It is dangerous and illegal to re use disposable non returnable reclaim cylinders or attempt to refill them When reclaim cylinders are empty evacuate th...

Page 8: ...ximum tolerance is 5 mm in both axes there is adequate space above the unit for air flow and to ensure access to the components see dimensional drawings the number of support points is adequate and th...

Page 9: ...2 577 18 TD 120 to 150 X mm Y mm Z mm 841 31 521 7 563 33 TD 200 to 300 Unit with grille protection option X mm Y mm Z mm 798 25 568 22 577 18 NOTES 1 Material self adhesive vinyl 9800 2 The symbols m...

Page 10: ...an installation For the location of fixing points weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings B In multiple unit installations maximum four...

Page 11: ...e location of fixing points weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings B In multiple unit installations maximum four units the side cleara...

Page 12: ...st when designing an installation For the location of fixing points weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings B In multiple unit installa...

Page 13: ...r the location of fixing points weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings B In multiple unit installations maximum four units the side cl...

Page 14: ...For the location of fixing points weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings B In multiple unit installations maximum four units the side...

Page 15: ...HT 1321 2122 ht 300 MINI VOIR NOTICE D INSTALLATION REFER TO INSTALLATION MANUAL Unit with grille protection option 3 7 Multiple unit installation Solid wall Solid wall NOTE If the walls are higher th...

Page 16: ...ter side operating pressure plus hydraulic module kPa 400 400 400 400 400 400 Fans Axial with rotating shroud Quantity 1 1 1 1 2 2 Maximum total air flow l s 3748 3736 4035 4036 7479 8072 Max speed st...

Page 17: ...pressor I Nom I Max I Max LRA 1 LRA 2 Cosine 080 100 120 150 200 300 Un Un 10 A A phi max ZH24KVE 13 6 18 3 20 3 99 51 0 85 1 ZH33KVE 17 3 24 2 26 9 127 66 0 85 1 2 ZH40KVE 20 4 30 0 33 2 167 87 0 89...

Page 18: ...of the machines The operating environment for the TD units is specified below 1 Environment 1 Environment as classified in EN 60721 corresponds to IEC 60721 outdoor installation 1 ambient temperature...

Page 19: ...1 120 3 8 3 8 150 4 6 4 6 200 5 9 6 4 300 6 1 8 5 1 Maximum flow rate at an available pressure of 20 kPa minimum 2 Maximum flow rate at a water temperature difference of 3K in the plate heat exchanger...

Page 20: ...hieve this volume it may be necessary to add a storage tank to the circuit This tank should be equipped with baffles to allow mixing of the fluid water or brine Please refer to the examples below Bad...

Page 21: ...llation practises for units installed outside have been applied in accordance with IEC 60364 table 52C No 17 suspended aerial lines No 61 buried conduit with a derating coefficient of 20 The calculati...

Page 22: ...able wire Max connectable section Min wire section Max wire section Section mm2 Section mm2 Max length m Wire type Section mm2 Max length m Wire type 080 1 x 10 1 x 6 100 XLPE Cu 1 x 10 245 PVC Cu 100...

Page 23: ...he disturbance of the oxygenation conditions encou rages destabilisation of copper hydroxides and enlarge ment of particles Electric conductivity 10 600 S cm pH Ideal case pH neutral at 20 25 C 7 5 pH...

Page 24: ...sed Open It is recomended to use a primary glycol loop for low temperature applications as shown below 2 1 3 Water network Unit Legend B Primary glycol loop minimum 10 C Intermediate heat exchanger D...

Page 25: ...e information for the pump inlet see Control manual I Temperature sensor Note Provides temperature information for the water type heat exchanger outlet see Control manual J Temperature sensor Note Pro...

Page 26: ...he heat exchanger leaving piping F Shut off valve G Available pressure pump H Temperature probe BPHE inlet Note Gives heat exchanger entering temperature information see installation manual I Pressure...

Page 27: ...hydraulic circuit presence of solid contaminants Take another reading Compare this value to the initial value If the pressure drop has decreased this indicates that the screen filter must be removed...

Page 28: ...units are given for the higher variable speed of the pump maximum available pressure Data applicable for Fresh water 20 C In case of use of the glycol the maximum water flow is reduced For pure water...

Page 29: ...standard configuration It can also be located in the leaving water In this case two additional sensors must be added on the common piping All parameters required for the master slave function must be...

Page 30: ...ctivated after a shut down of the heat pump following a fault condition safety device This requires only a 400 V 3 ph 50 Hz power supply source For the required configuration of the stages consult the...

Page 31: ...um energy efficiency Pa 90 195 Nominal speed rpm 710 966 Specific ratio 1 002 1 002 Relevant information to facilitate the disassembly recycling or removal of the product at the end of life See servic...

Page 32: ...matically reset high pressure safety switches calibrated to 3130 kPa relative pressure soft alarm is manually reset NOTES Monitoring during operation Follow the regulations on monitoring pressurised e...

Page 33: ...time equalisation Lon gateway Two directional communication board complying with Lon Talk protocol Connects the unit by communication bus to a building management system Bacnet over IP Two directiona...

Page 34: ...2 Applicable rules for units incorporated into an air duct system Ensure that the suction or discharge inlets are not accidentally obstructed by the panel positioning e g low return or open doors etc...

Page 35: ...the electrical protection devices Check the correct operation of all heaters Replace the fuses every 3 years or every 15000 hours age hardening Check that no water has penetrated into the control box...

Page 36: ...ump if service considerations allow this Clean evaporators guarantee optimal operation of your unit Cleaning is necessary when the evaporators begin to become fouled The frequency of cleaning depends...

Page 37: ...4 5 35 19 40 41 24 55 55 59 94 5 25 2 94 9 11 14 75 35 83 41 03 24 25 56 01 60 37 5 5 4 19 10 33 15 36 46 41 64 24 5 56 46 60 8 5 75 5 4 11 5 15 25 37 08 42 24 24 75 56 9 61 22 6 6 57 12 65 15 5 37 7...

Page 38: ...pected for crossed wires All plug assemblies are tight Check air handling systems All air handlers are operating All water valves are open All fluid piping is connected properly All air has been vente...

Page 39: ...tion of l s Carry out the QUICK TEST function see Aquaciat Cal o TD Connect Touch control manual Check and log on to the user menu configuration Load sequence selection Capacity ramp loading selection...

Page 40: ...ce Printed in the European Union Manufacturer reserves the right to change any product specifications without notice CARRIER participates in the ECP programme for LCP HP Check ongoing validity of cert...

Reviews: