CIAT AQUACIAT CALEO CONNECT TOUCH Instruction Manual Download Page 23

7  -  STANDARD CONTROL OPERATIONS AND OPTIONS

7.4  Water pump control

The unit can control one water exchanger pump which can be 
either a fixed speed pump or a variable speed pump. 

The pump can be factory-installed (“internal pump”) or it can be 

supplied by the customer (“external pump”).

Pump control logic Internal pump

External pump

Constant speed control

yes

-

Variable speed control

yes

yes

The pump is normally turned on when the unit is running in Heating 
mode. The pump control method may vary depending on the 

type of the pump (internal or external) and the pump control logic 

set by service technicians. When the unit is “Off”, the pump is 

stopped; however, the pump can be started in particular operating 
conditions when freeze protection of the heat exchanger is active 

(see section 7.4.3).

7.4.1  Constant speed control

Fixed speed pump can be controlled through the “Pump 1 Output” 
parameter  in  the  Outputs  menu.  Fixed  speed  pump  control 

applies only to internal pumps.

7.4.2  Variable speed control

The  water  flow  is  controlled  based  on  Delta  T  (differential 
temperature) on the water exchanger; however, the control logic 
may differ depending on the type of the pump (internal/external).

Variable speed control

Internal pump

External pump

LEN drive

yes

-

0-10V drive: Step control

-

yes

0-10V drive: PID control

optional

yes

Internal pump control

The speed of the internal pump may vary depending on the current 

unit capacity and service configuration. For example, in defrost 
mode  higher  pump  speed  equals  better  efficiency;  therefore, 
during defrost the pump speed will be set to the maximum speed 

that is allowed. At the same time, when the unit is running, but 
there is no heating demand, the pump speed will be low. 

Under normal operating conditions, the unit’s nominal water flow 

should correspond to the minimum pump speed.

Depending on factory installation, the internal pump can be 
controlled either through the standard LEN drive or the optional 
0-10V drive. The internal pump control can be set only by 
service technicians.

When controlled through the LEN drive:

• 

The status of the internal pump is displayed in the Pump 
Status menu under “Drive pump status”. 

• 

“External Pump Output” (PUMP_EXT, Pump Status menu) 
and “External Pump Output” (PUMP_EXT, Outputs menu) 

will be set to “0”.

When controlled through the 0-10V drive:

•  The drive output is controlled through 0-10V output, 

i.e. “External Pump Output” (PUMP_EXT, Outputs menu).

• 

“External Pump Output” (PUMP_EXT, Pump Status menu) 

displays its value in %.

• 

The output is controlled by a PID to satisfy the Water Delta T 
Setpoint defined by service technicians. When the unit is 

ready, the pump speed is set to pump saving speed 
(minimum pump speed). When the unit is running, water 
pump speed is clamped between the minimum and 

maximum pump speed.

External (customer) pump control

The control allows for managing the external 0-10V pump via 
the 0-10V Pump Config menu (FLOWCONF).

When controlled through the 0-10V drive:

• 

The pump is controlled through 0-10V output, i.e. “External 
Pump Output” (PUMP_EXT, Outputs menu).

• 

“External Pump Output” (PUMP_EXT, Pump Status menu) 

displays its value in %.

The customer pump can be controlled by: 

• 

Step control logic: 

•  a step value is added to the output each time the 

“Reschedule timer” has elapsed and 

Delta T > Water Delta T Setpoint [dt_stp] + Deadband 

•  a step value is removed from the output each time the 

“Reschedule timer” has elapsed and 

Delta T < Water Delta T Setpoint [dt_stp] - Deadband 

• 

PID control logic:

 

The output is controlled by a PID to 

satisfy Water Delta T Setpoint.

To set 0-10V pump control method

1. Navigate to the Configuration menu.
2. Select 

0-10V Pump Config 

(FLOWCONF).

3. Set the pump control logic [logictyp].

Logic: 0=No,1=STEP,2=PID [logictyp]
0 = no (no external pump)

1 = Step control logic

2 = PID control logic

7.4.3  Pump protection (pump anti-stick function)

The control provides a means to automatically start the pump 
each day at 14:00 for 2 seconds when the unit is off. 

Starting  the  pump  periodically  for  a  few  seconds  extends  the 

lifetime of the pump bearings and the tightness of the pump seal. 

To set pump automatic rotation delay

1. Navigate to the Configuration menu.
2. Select 

Pump Configuration

 (PUMPCONF).

3. Set 

Pump Sticking Protection 

[pump_per] to “yes”.

Pump Sticking Protection [pump_per]
no/yes

yes

 

 

EN - 21 AQUACIAT

CALEO

Summary of Contents for AQUACIAT CALEO CONNECT TOUCH

Page 1: ...Instruction manual AQUACIAT CALEO 14 300 02 2018 10199 CONNECT TOUCH...

Page 2: ...he user interface provided in this manual include text in English After changing the language of the system all labels will be in the language selected by the user Please read all instructions prior t...

Page 3: ...ouch buttons 5 4 4 Menu structure 6 5 SETTING UP CONNECT TOUCH CONTROL 7 5 1 General description 7 5 2 Welcome screen 7 5 3 Synoptic screen 7 5 4 Unit start stop 7 5 5 Display settings 8 5 6 Main menu...

Page 4: ...power source RISK OF BURNS Electrical currents may cause components to get hot Handle the power cable electrical cables and conduits terminal box covers and motor frames with great care 2 1 Control sy...

Page 5: ...d to monitor the water pressure The pump is protected against cavitation low pump entering pressure 3 5 Temperature sensors Temperature sensors constantly measure the temperature of various components...

Page 6: ...sed to control the pump and unit operation open pump continues to run closed pump is stopped unit is not allowed to start DHW Tank Request Switch SIOB DI 06 63 64 Used to command the domestic hot wate...

Page 7: ...ernet connector 3 Modbus RS485 connector 4 Internal bus RS485 5 Power supply connector 24 VAC This RS 485 bus can be used as a second internal bus for the connection of gateway If it is the case then...

Page 8: ...Configuration User Configuration Pump Configuration Date Time 0 10V Pump Config Heat Cool Config Control Identification Schedule Configuration menu Main menu ModbusRTU Config ModbusTCP IP Config Netwo...

Page 9: ...ng the table content ACCESS DENIED Equipment controller denies access to one of the tables LIMIT EXCEEDED The value entered exceeds the parameter limit Save changes Modifications have been made The ex...

Page 10: ...tem allows users to add new languages to the control To learn more about language customization please contact your local service representative 5 5 2 System of measurement The control offers the poss...

Page 11: ...modifiable parameters such as pump configuration schedule menu etc The Configuration menu is password protected To access the Configuration menu press the Main menu button located in the upper left pa...

Page 12: ...HEDULE 3 Go to OCCPC01S 4 Select appropriate check boxes to set the unit occupancy on specific days 5 Define the time of occupancy 6 When the time schedule is set the selected period will be presented...

Page 13: ...the unit cannot be started stopped via the web interface All other operations including monitoring unit parameters or unit configuration can be performed via the web browser interface 5 10 2 Web brow...

Page 14: ...t selection 5 0 Auto 1 Spt1 2 Spt2 0 Auto schedule control 1 Heating setpoint 1 2 Heating setpoint 2 6 SP_OCC no yes Setpoint Occupied Setpoint occupancy status 7 CHIL_S_S disable enable Net Cmd Start...

Page 15: ...kPa Eco Suction Pressure Economizer suction pressure 4 5 INTERNAL HYDRONIC MODULE Internal hydronic module 6 W_P_IN kPa Inlet Water Pressure Inlet water pressure Displayed in French by default Setpoi...

Page 16: ...utput 17 ALARM off on Alarm Relay Status Alarm relay status 18 RUNNING off on Running Relay Status Running relay status 19 DHW_3WV off on DHW 3 Way Water Valve DHW 3 way water valve Displayed in Frenc...

Page 17: ...splayed in French by default Domestic Hot Water Menu DHW_STAT No Name Status Default Unit Displayed text Description 1 dhw_mode 0 to 2 Mode Mode 2 0 SHC 1 DHW 2 AntiLeg 0 Space Heating Control SHC 1 D...

Page 18: ...de additional features some tables may contain parameters that cannot be configured for a given unit General Config Menu GENCONF No Name Status Default Unit Displayed text Description 1 ramp_sel no ye...

Page 19: ...set Value OAT max reset value 3 dt_hr_no 0 to 14 0 K Delta T No Reset Value Delta T no reset value 4 dt_hr_fu 0 to 14 0 K Delta T Full Reset Value Delta T max reset value 5 I_hr_no 0 to 20 0 mA Curren...

Page 20: ...tware version 4 xx chars MAC address Serial Number Serial number MAC address Displayed in French by default 0 10V Pump Config Menu FLOWCONF No Name Status Default Unit Displayed text Description 1 log...

Page 21: ...Parity High 4 Force Parity High 17 stop_bit 0 to 1 0 Stop bit Stop bit 18 0 One Stop Bit 0 One Stop Bit 19 1 two Stop Bits 1 Two Stop Bits 20 real_typ 0 to 1 1 Real type management Real type managemen...

Page 22: ...y can never exceed the limit setpoint activated by these contacts The limit setpoints can be modified in the SETPOINT menu By setting DEM_LIM when the unit is in Network mode By lag limit set by the m...

Page 23: ...d through the LEN drive The status of the internal pump is displayed in the Pump Status menu under Drive pump status External Pump Output PUMP_EXT Pump Status menu and External Pump Output PUMP_EXT Ou...

Page 24: ...trol point is modified so that the machine capacity required is adjusted to be as close as possible to the demand The reset source can be provided by one of the following Outdoor air temperature that...

Page 25: ...ng mode if at least one of the following conditions applies The volt free tank request contact is open The maximum operating time for the DHW mode has elapsed Time schedule 3 is in an unoccupied perio...

Page 26: ...eating stage will not be used even if the heating demand cannot be satisfied This electric heating backup option can be enabled by setting 1 Elec Stage For Backup ehs_back to yes in the Heat Cool Conf...

Page 27: ...ory Basic Reset Alarms User 8 2 Displaying current alarms The Current alarms menu may display up to 10 current alarms To access the list of currently active alarms 1 Press the Alarm button in the uppe...

Page 28: ...e 15 4901 Loss of communication with SIOB Board Number A Bus installation fault communication error Unit shuts down Automatic if communication is re established 16 4601 Loss of communication with AUX1...

Page 29: ...company Maintenance date passed No action alert Automatic if the new maintenance date is set 37 8000 Initial Factory Configuration Required No factory configuration Unit cannot be started Automatic if...

Page 30: ...ed increase Contact Manufacturer Agency 38 over current during product speed decrease Contact Manufacturer Agency 39 over current during product speed hold Contact Manufacturer Agency 41 drive type er...

Page 31: ...erious damage can occur to your equipment TheManufacturerprovidesawiderangeofservicecontractswhich embrace the assistance of highly qualified HVAC engineering professionals ready to help if needed The...

Page 32: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Reviews: