Ice Combo Technical Manual

Summary of Contents for Ice Combo

Page 1: ...Ice Combo Technical Manual...

Page 2: ...Point Procedure 1 Check T R input is AC110V on the PCB Board Pic ex Check white red wire connection 2 Check Operation Switch is ON Check Power Switch is ON Pic 1 1 Power Defect Power Switch Operation...

Page 3: ...Check Point Procedure 1 Check Compressor Temperature Normal temperature during ice making 158 176 F 1 2 Compressor Defect...

Page 4: ...Check Point Procedure 1 Check Wire Condenser Temperature Normal temperature during ice making 122 140 F 1 3 Wire Condensor...

Page 5: ...Check Point Procedure 1 Check Dryer Temperature Normal temperature during ice making 41 59 F Note Should be warm when you grab it COLD during ice dispensing 1 4 Dryer Blocking...

Page 6: ...floating If Bi Metals overlapped as in the Abnormal Picture adjust them as in the Normal Picture Hot water overflow is caused by higher hot temperature due to the two Bi Metal s overlapping 1 5 Hot W...

Page 7: ...Procedure Particles may be clogged on the Silicon Mesh at the Nozzle connection 1 Once 6 mo A S Term Check the Mesh and clean or replace it 2 Do Not clean water tank AFTER Mesh replacing 2 1 Nozzle Me...

Page 8: ...2 2 Squashed Tee Silicon Check Point Procedure 1 Nozzle injection weakness is caused by kinked silicon tube connect to the Circulation Pump 1 Replace Tee Silicon to Tee Pipe...

Page 9: ...2 3 Nozzle Silicon Leak Check Point Procedure 1 Water shortage caused by Nozzle Silicone Tube 2 S Type Connection leaking 1 Tighten with Spring Clip at the Nozzle Silicon Tube 2 S Type connection...

Page 10: ...2 4 Curtain Defect Check Point Procedure 1 Water shortage caused by Curtain Gap 1 Replace Curtain...

Page 11: ...rowed area while ice making Normally below 50 F When 2 or 3 ice cubes are not be made out of 12 1 If the Hot Gas V V Out area is higher than 50 F during ice making press ON OFF Ice dispensing button a...

Page 12: ...adient Check Check Point Procedure 1 Irregular Dryer gradient interrupts flows of refrigerants Normal Dryer gradient is 15 In case of ice cubes shape is getting worse 1 Correct the Dryer s gradient as...

Page 13: ...7 Ice Making Correction Check Point Procedure 1 In case of abnormal ice cubes size Below 80 of normal 1 Change the Dip switch from 2 to 1 2 down first then 1 up 100 70 Factory Setting is 2 Switch to...

Page 14: ...When it stops making ice the Ice Full LED turns ON Ice Full LED turns ON although the ice tank is still empty 2 Mi com Rev 2 stops making ice for 8 hours after the Ice Full LED turns ON 3 Method to t...