Chromatic HCV Valve Installation, Operation And Maintenance Manual Download Page 2

Installation

Identify  the  valves  with  the  packing  list  and  applicable 
documents  against  the  name  plate  for  proper  identification. 
Check  the  total  equipment  weight  and  use  suitable  handling 
devices to safely install the valves.

Prior to installation, ensure the valve drain and bleed plugs are 
installed and tightened securely and the valve is in the full open 
position.

Valves shall be installed in a manner that will not support the 
weight  of  the  line  and  line  expansion  and  strain  is  isolated 
external to the valve. Install the valve with the preferred inlet, 
marked  by  the  red  flange  and  marking  on  the  valve  body, 
toward  the  pump  or  pressure  source.  Position  the  valve  in 
piping to allow clearance and access to the operator. The valve 
should  be  installed  that  the  drain  and  bleed  plugs  are 
accessible and cartridge removal is possible for in-line service 
and  maintenance.  The  preferred  orientation  is  with  the  drain 
plug to be at the lowest point of the valve.

Flanged valves should be installed using the proper gasket (not 
supplied)  and  procedure  recommended  by  National  and 
International  Standards/Codes  specified  for  the  installation. 
Butt  Weld  ends  shall  be  welded  in  accordance  to  proper 
Standard Code welding procedures.

Piping should be thoroughly flushed with the valve in the open 
position  prior  to  valve  operation  and  the  body  drained  after 
testing  to  remove  test  fluid  and  debris  that  may  have 
accumulated in the body during testing.

Install  the  valve  operator  according  to  the  manufacturer’s 
guidelines. Refer to pneumatic, hydraulic or electric actuators 
section for setting or adjusting the open and close stops for the 
operator.

Operate  (dry  run)  the  valve  by  cycling  from  open  to  closed 
position several times to test and ensure the proper operation 
of the valve.

Operations

Prior  to  valve  operation,  make  sure  that  the  valve  has  been 
installed in the pipeline with the preferred inlet upstream in the 
normal flow direction. The valve is bi-directional and will seal in 
either  direction.  Operating  the  valve  in  a  preferred  or  normal 
flow  direction  will  provide  optimum  sealing  performance  and 
seal life, especially in dirty or contaminated fluids.

The  valve  operates  90°  from  the  full  open  to  full  closed 
position. The valve is a torque seated valve with the maximum 
closing  torque  for  the  appropriate  pressure  is  applied  at  the 
end  of  the  close  cycle.  Under  high  differential  pressures,  the 
un-seating torque may be as high as the seated torque.

Pneumatic, Hydraulic or Electric Actuators

In  the  case  when  the  actuator  has  been  installed  prior  to 
receipt  or  installation,  check  that  air,  hydraulic  and  electrical 
supply  lines  are  connected  per  the  manufacturer’s 
specifications  and  instructions.  Using  the  manual  override, 
place  the  valve  in  the  mid  open  position.  Verify  that  the 
actuator  mounting  bolts  are  securely  tightened.  Activate  the 
OPEN button or switch and make sure that the actuator travel 
counterclockwise  towards  the  open  position.  If  it  does  not, 
make  the  appropriate  piping  or  wiring  changes  and/or 
adjustments.

In the case when an actuator has not been previously installed 
on the valve, mount the actuator and tighten the nuts on the 
studs securely to the proper torque specification per Table 1. 
Install  the  pneumatic  or  electrical  wiring  and  cable  to  the 
actuator  according  to  the  manufacturer’s  instructions.  After 
installation of the operator on to the valve, rotate the position of 
the ball approximately 1⁄4 turn to determine if the ball moves to 
the  closed  position.  If  the  ball  does  not  completely  close  the 
port, adjust the actuator stop to reposition the valve’s closed 
position. Turn the actuator to the open position and observe if 
the  Hemi  moves  completely  to  the  open  position.  A  full  port 
opening  should  be  visible.  If  the  Hemi  does  not  completely 
move  to  the  open  position,  adjust  the  actuator  stop  to 
reposition the valve’s open position. The Hemi should be in the 
full open position at zero degrees.

Maintenance

The valve does not require periodic lubrication or maintenance 
to  provide  continuous  trouble-free  service.  The  valve  is  a 
torque  seated  valve  and  maximum  rated  torque  must  be 
applied  in  the  closed  position.  If  the  valve  does  not  seal 
properly, or if there are difficulties opening or closing the valve, 
it may be due to foreign material deposits within the cartridge 
of the valve body. Cleaning may be required in order to remove 
the debris or foreign objects.

HCV

 Valve

CAUTION: 

Do not attempt to operate the valve past the full open 

and closed position. Adjust the operator stops to engage prior to 
the valve integral stops, as the integral stops in the valve are not 
intended to be used as the operator stops.

NOTE: 

Do not over torque in the closed position. Over torque 

may cause damage to the valve and void the warranty.

2         IOM HCV 001 09-2019A

Reviews: