background image

OPERATION

Important: NWHOSR/NWHSRG Circulation Heaters
are equipped with INCOLOY

®

heating elements and

cast iron heating chambers (galvanized for the
NWHSRG). It is the responsibility of the purchaser of
the heater to know the chemical composition of the
corrosive solution and the character of the materi-
als entering the solution as well as the corrosive
effect of the solution upon the heating elements
and chamber.

Sheath corrosion can result in a ground fault which
depending upon the solution being heated, can
cause an explosion or fire.

If the heater is not properly submerged, the heat-
ing elements will overheat and could result in a fire
or damaged equipment.

1.

Do not heat solutions that are corrosive to the heating element
sheath or the heating chamber.

2.

Terminal ends of heater must be protected from drippings, con-
densation, spray or direct spill-over of material. Their presence
at the terminals may damage heater electrical insulation. 

3.

If foreign material is carried by the liquid flow, install suitable
filters in the inlet pipeline to the heater. Liquid flow to the
heater should be free of suspended solids.

4.

Do not allow heater to operate when liquid flow is interrupted.

5.

The NWHSRG/NWHOSR is designed as a flow through
heater. The chamber 

must

be full for safe operation.

PRE-OPERATION

1.

Follow the instructions for operation of your application.
Ensure your procedure includes:

A.

Make sure all electrical and piping connections are tight.

B.

Remove all air from the heater and piping.

MAINTENANCE

ELECTRIC SHOCK HAZARD. Disconnect all power
before servicing heater. Failure to do so could
result in personal injury or property damage.
Heater must be serviced by a qualified person in
accordance with the National Electrical Code.
NFPA 70.

1.

Remove heating element assembly periodically to check heater
sheath for sealing, corrosion or excessive oxidation. Correct
operating conditions to minimize sheath deterioration. Refer to
warnings in operation section.

2.

Drain heater periodically to remove sludge deposit. Deposits
can act as an insulator and shorten heater life.

Note: 

User is responsible for maintenance schedule based on

their knowledge of the heated medium and operating conditions.

3.

Periodically check temperature control operation to insure
accurate and safe process operation.

4.

Check all electrical connections periodically and retighten con-
nections which may have loosened in service. Replace wire
and wire terminals which show signs of oxidation which would
interfere with establishment of reliable electrical connections.

5.

Correct any excessive leaking. Also refer to the last step in the
installation section regarding adequate collection/drainage.

6.

Reinstallation steps.

A.

Reseal thread fittings with adequate seal material for the
pressure/temperature rating on your heater.

B.

Refer to the pre-operation section.

7

Summary of Contents for VERSATHERM PE414-3

Page 1: ...ss ELECTRIC SHOCK HAZARD Disconnect all power before installing or servicing heater Failure to do so could result in personal injury or property dam age Heater must be installed or serviced by a qualified person in accordance with the National Electrical Code NFPA 70 The system designer is responsible for the safety of this equipment and should install adequate back up controls and safety devices ...

Page 2: ... not fail safe it should not be used for temperature limiting duty Wiring to this device is the responsibility of the user FIRE HAZARD Since heaters are capable of devel oping high temperatures extreme care should be taken to A Provide minimum of 6 spacing from chamber and related piping to nearest combustible mate rial B Do not operate near combustible fluids or in combustible vapor or gas laden ...

Page 3: ...mine the appropriate wiring diagram for your heater instal lation Figure 1 may be referenced as a general diagram of how a contactor and temperature control are used in conjunction with the specific wiring diagrams 6 Use ground fault protection equipment where electrical insula tion failure can cause process problems 7 When element wattages are not equal heaters must not be con nected in series 8 ...

Page 4: ...der your PCN number you must know the kW and watt density watts sq in needs for your application Step 3 Note the Wiring diagram for your selection Step 4 Go to Wiring Diagram sheet Peel off the diagram that matches the in step 3 Stick this to the inside of your electrical enclosure Step 5 Peel off corresponding Volts circuit phase and kW info from the Wiring Diagram sheet and stick to the designat...

Page 5: ... 1 3Ph 13 amps 11 3 20kW 240V 2 1Ph 2 x 42 amps 80 8 20kW 240V 2 3Ph 2 x 25 amps 80 2 PCN 100044 054 304745 004 PCN 100360 054 304745 404 3 0kW 120V 1 1Ph 25 amps 20 13 3 0kW 208V 1 3Ph 9 amps 20 12 6 0kW 120V 1 1Ph 2 x 25 amps 20 8 6 0kW 208V 1 3Ph 17 amps 20 4 6 0kW 208V 2 3Ph 2 x 9 amps 20 5 12kW 240V 1 3Ph 29 amps 78 11 24kW 240V 3 1Ph 3 x 34 amps 78 9 24kW 240V 2 3Ph 2 x 29 amps 78 2 Half of ...

Page 6: ...K 1L2 2L1 2L2 1L1 Y E L L O W B L U E R E D Y E L L O W B L U E R E D O R A N G E B R O W N B L A C K O R A N G E B R O W N B L A C K L1 L2 Y E L L O W B L U E R E D O R A N G E B R O W N B L A C K Y E L L O W B L U E R E D 3L1 B L A C K R E D 3L2 B L A C K R E D 1L1 B R O W N O R A N G E 1L2 B R O W N O R A N G E 2L1 Y E L L O W B L U E 2L2 Y E L L O W B L U E B L A C K R E D B R O W N O R A N G ...

Page 7: ...tructions for operation of your application Ensure your procedure includes A Make sure all electrical and piping connections are tight B Remove all air from the heater and piping MAINTENANCE ELECTRIC SHOCK HAZARD Disconnect all power before servicing heater Failure to do so could result in personal injury or property damage Heater must be serviced by a qualified person in accordance with the Natio...

Page 8: ...304748 005 NWHSRG 06 040P E1 100095 156 304748 006 NWHOSR 06 04P5 E2 100255 156 304748 301 NWHOSR 06 04P5 E2 100263 156 304748 302 NWHOSR 06 005P E2 100271 156 304748 303 NWHOSR 06 006P E2 100280 156 304748 304 NWHOSR 06 006P E2 100298 156 304748 305 NWHOSR 06 010P E2 100300 156 304748 306 NWHSRG 06 018P E2 100327 156 304748 301 NWHSRG 06 018P E2 100343 156 304748 302 NWHSRG 06 020P E2 100351 156 ...

Reviews: