background image

Dimensions (In.)

Watt

Model

Voltage Phase  kW 

Density

A

B

C

NWH-3625

1 or 3

Δ

6

47.7

32-15/16

22-1/2

16-1/2

NWH-3925

1 or 3

Δ

9

47.5

32-15/16

22-1/2

16-1/2

NWH-31225

1 or 3

Δ

12

46.2

42-15/16

32-1/2

26-1/2

NWH-31525

1 or 3

Δ

15

45.9

55-7/16

45

39

NWH-31825

1 or 3

Δ

18

45.6

55-7/16

45

39

Chromalox

®

DIVISION  

4

                                      SECTION  

NWH

SALES

REFERENCE

DATE

SERVICE REFERENCE

Installation Operation

and

RENEWAL PARTS IDENTIFICATION

PE405-6

JULY, 1990

(Supersedes PE405-5)

161-048380-001

GENERAL

INSTALLATION

© 2010 Chromalox, Inc.

Type NWH-3

Circulation Heater

for Water Heating

The NWH-3 series is a general-purpose water or water-based

solution circulation heater intended for use indoors. It is designed
for 150 psig at 550˚F per ANSI standards.

The 3 copper-sheathed tubular elements are centered in a 3”

diameter galvanized steel heating chamber and welded to a
removable galvanized steel flange. The assembly is surrounded
by 1-1/2” insulation and sheet metal jacket.

Depending upon the order specifications, the NWH-3 may or

may not be factory equipped with an AR or other Chromalox

thermostat. Such thermostats function to control outlet tempera-
tures and to limit internal temperatures under abnormal flow con-
ditions. These controls do not fail safe.

CAUTION: 

Users should install adequate back-up controls

and safety devices with their electric heating equipment.
Where the consequences of failure may be severe, back-
up controls are essential. Although the safety of the
installation is the responsibility of the user, Chromalox
will be glad to make equipment recommendations.

CAUTION: 

Hazard of Electric Shock. Disconnect all

power before installing heater.

1. Vertical Mounting 

(Preferred) —

When the heater is vertically mounted, the terminal housing 
will be at the top of the heater. The water inlet pipe will be located on
the side near the bottom of the heater and the outlet pipe at the top.

The axis of the chamber will be in a vertical position as in
the photo above, and as in Figure A.

Note:

A drain pipe located at the bottom of the heater should

be provided and enough room left, when mounting heater, to
allow draining the heater.

2. Horizontal Mounting

(Optional) —

When mounting heater horizontally, inlet and outlet pipes

must

be up. In any other position, heater cannot be purged of air,

and elements may be seriously damaged. (See Figure B.)

Specifications — Table A

Incorrect

Correct

Figure A — Vertical Mounting

Figure B — Horizontal Mounting

Correct

Incorrect

A

C

B

F

12-5/16”

Thermostat

Type AR

Mounting Lugs

3/8” - 16

Threaded Holes -

1-1/2” Deep

1-1/4” Centers

1” Pipe Inlet

1” Pipe

Outlet

1-3/8” Conduit

Openings

D

240

or

480

E

Summary of Contents for NWH-31225

Page 1: ...ns These controls do not fail safe CAUTION Users should install adequate back up controls and safety devices with their electric heating equipment Where the consequences of failure may be severe back up controls are essential Although the safety of the installation is the responsibility of the user Chromalox will be glad to make equipment recommendations CAUTION Hazard of Electric Shock Disconnect...

Page 2: ...h establishment of reliable electrical connections WIRING WARNING Hazard of Electric Shock Any installation involving electric heaters must be effectively ground ed in accordance with the National Electrical Code to eliminate shock hazard 1 Be sure line voltage matches heater voltage on nameplate 2 Electric wiring to heater must be installed in accordance with local and National Electrical Codes 3...

Page 3: ... 024796 014 300 057560 007 NWH 31525 240 1 15 155 024796 016 300 057560 007 300 048481 006 NWH 31525 240 3Δ 15 155 024796 017 300 057560 007 300 048481 006 NWH 31525 480 1 15 155 024796 018 300 057560 007 300 048481 006 NWH 31525 480 3Δ 15 155 024796 019 300 057560 007 300 048481 006 NWH 31825 240 1 18 155 024796 021 300 057560 007 300 048481 006 NWH 31825 240 3Δ 18 155 024796 022 300 057560 007 3...

Page 4: ...UT 84404 Phone 1 800 368 2493 www chromalox com PL U0 T3 Litho in U S A Limited Warranty Please refer to the Chromalox limited warranty applicable to this product at http www chromalox com customer service policies termsofsale aspx ...