CS3 Three Phase SSR Quick Start Manual

 0037-75554 (PK528)

This manual is intended to provide only the basic installation and operation instruc-

tions for the CS3 Three Phase Solid State Relay. Please refer to manual PK522, for 

complete installation & operation details. The most current revision of PK522 may be 

found on the Chromalox website: www.chromalox.com

 1. IMPORTANT SAFEGUARDS

ELECTRIC SHOCK HAZARD: Read and understand all instructions before 

installing, servicing or operating this controller. Failure to do so could 

result in equipment or property damage as well as personal injury and 

even death.

HIGH VOLTAGE is used in the operation of this equipment. DEATH ON 

CONTACT may result if personnel fail to observe safety precautions. 

Learn the areas containing high-voltage connections when installing or 

operating this equipment.

Be careful not to contact high-voltage connections when installing or 

operating this equipment. Before working inside the equipment, turn 

power off and ground all points of high voltage potential before touch-

ing.

ELECTRIC SHOCK HAZARD. Any installation involving control equip-

ment must be performed by a qualified person and must be effectively 

grounded in accordance with the National Electrical Code to eliminate 

shock hazard. 

The Owner/Installer must provide all necessary safety and protection 

devices and follow all current electrical wiring standards and regula-

tions. Failure to do so may compromise the integrity of the controller 

and/or cause product failure resulting in a safety risk to operational 

service and personnel.

This controller utilizes a heat sink which is designed to cool the unit 

during operation. Under no circumstance should air flow around the 

controller be compromised in any way. Failure to do so may result in the 

overheating of the controller, product failure, product temperatures and 

even fire.

During continuous operation, the heat sink can reach a very high tem-

peratures, and keeps a high temperature even after the unit is turned 

off due to its high thermal inertia.
Higher voltages may be present. DO NOT work on the power section 

without first disconnecting electrical power to the panel. Failure to do 

so could result in serious injury or death.

 2. INSTALLATION - MECHANICAL

To ensure proper performance, maximum safety and reliability, it is essential to install 

the unit correctly. This includes proper mounting, spacing, hardware and wiring. See 

below:
1.  Maximum surrounding air temperature is 40°C in “Open Type Equipment” which 

is suitable for use in pollution degree 2.

2.  Install the unit vertically (max 10° inclination from vertical axis).

3. Spacing:

  –Min. vertical distance between unit and panel wall: 3.9” (100 mm)

  –Min. horizontal distance between unit and panel wall: 0.8” (20 mm)

  –Min. vertical distance between adjacent power control units: 11.8” (300 mm)

  –Min. horizontal distance between adjacent power control units: 0.8” (20 mm)

 3. INSTALLATION – ELECTRICAL CONTROL, LOAD & LINE CONNECTIONS & LED INDICATION

CS3 with VDC Control Signal Input

CS3 with VAC Control Signal Input

Dimensions & Weights

1/L1

3/L2

5/L3

AC51: 25A
AC53a: 5A

CS3-02548-110

On

L1 L2 L3 A1+

T1 T2 T3 A2-

Alarm

B1
B2

A1

A2

2/T1

4/T2

6/T3

1/L1

3/L2 5/L3

AC51: 40A    600V ac
AC53a: 8A    50/60Hz

CS3-04060-112

On

L1 L2 L3 A1+

T1 T2 T3 A2-

Alarm

B1
B2

A1

A2

2/T1

4/T2 6/T3

5” (127)

5” (127)

8

1.18” (30)

3.94 (100)

1.97” (50) Max

3.15” (80)

8

CS3 25A

CS3 40A / CS3 55A

Depth:

- Models CS3-xxxxx-1xx:  5.9” (150)

- Models CS3-xxxxx-2xx:  6.2” (158)

2.4lb (1100 g)

3.0 lb (1350 g)

1.18” (30)

1/L1

3/L2

5/L3

AC51: 40A
AC53a: 8A

CS3-04060-221

On

1 3 5

A1+

2 4 6

A2-

Alarm

B1
B2

A1

A2

2/T1

4/T2

6/T3

20-260

VAC/VDC

600 VAC

50/60 Hz

fan: 230 VAC

nc

nc

Out

AI

1/L1

3/L2

5/L3

AC51: 40A
AC53a: 8A

CS3-04060-111

On

1 3 5

A1+

2 4 6

A2-

Alarm

B1
B2

A1

A2

2/T1

4/T2

6/T3

5-32 Vdc

600 VAC

50/60 Hz

fan: 230 VAC

Label

Connection/Indication

Label

Connection/Indication

L1, L2, L3 Line 1, Line 2, Line 3 VAC Input

B2

Alarm Output (Option)

T1, T2, T3 Load 1, Load 2, Load 3 VAC Input

ON

Red LED - Command Signal Indication

A1

(+) VDC Control Signal Input

Alarm

Yellow LED - Over Temp. Indication

A2

(-) VDC Control Signal Input

GND

Earth Ground (Not shown, varies by model)

B1

Alarm Output (Option)

Label

Connection/Indication

Label

Connection/Indication

L1, L2, L3 Line 1, Line 2, Line 3 VAC Input

ON

Red LED - Command Signal Indication

T1, T2, T3 Load 1, Load 2, Load 3 VAC Input

Alarm

Yellow LED - Over Temp. Indication

A1, A2

AC Control Signal Input

OUT-AL Red - LED Load/Line Interrupt Alarm

(Alarm Code 2 Only)

B1

Alarm Output (Option)

GND

Earth Ground (Not shown, varies by model)

B2

Alarm Output (Option)